IEC_BACNET_PRIORITY_ARRAY_ITEM (STRUCT)¶
TYPE IEC_BACNET_PRIORITY_ARRAY_ITEM : STRUCT
Description for type BACnetPriorityArray
A Priority Array is a property that is present in an object that contains a commandable Property (such as the present-value of an Output or Value object). A Priority Array has BACNET_MAX_PRI_ARRAY slots, each of which can contain a value for the commandable Property. For the object types supported in the present API version, the value contained in a Priority Array has one of the datatypes Null, Enumerated, Real, Unsigned…. See Section 19 of the ASHRAE Standard 135-2010 for a description of command prioritization using Priority Arrays. A Property Contents containing a single Priority Array Item or an entire Priority Array, will have its tag equal to DATA_TYPE_PRI_ARRAY_ITEM. The Elements-Number attribute of a Property Contents indicates whether it contains a single Priority Array Item or an entire array.
- InOut:
Name
Type
Comment
tagThis specifies the type of the contents in this array element
valueHolds the different possible values to be stored in this structure