EVT_BACNET_UNCONFPRIVATEXFER (STRUCT)¶
TYPE EVT_BACNET_UNCONFPRIVATEXFER : STRUCT
The UnconfirmedPrivateTransfer service hook.
This is the type declaration for the Unconfirmed-Private-Transfer service application hook. This hook allows a BACnet application to process Unconfirmed-Private-Transfer service since there are no default processing of this service in the present API version. This hook is given all of the parameters of a service request, and is responsible for all error checking (addresses correctness, Device/object existence and any other service parameter given). A pointer to the routine is registered with the application by BACnetSetHook(). A hook can be registered by the registering API routine at any time. One hook procedure is registered per service. If a hook is registered more than once for the same service, the new hook procedure replaces the old one. A NULL procedure pointer can be used to deregister hook. Because this is an unconfirmed service, no response is expected. This routine must complete its processing only by returning its Return Value. A hook frees all resources it requires, including all hook parameters. A hook can choose not to override the default API processing of a service request by returning the value CB_STATUS_DEFAULT.
- InOut:
Name
Type
Comment
pCBStatusPOINTER TO IEC_BACNET_CB_STATUS
CB-Status returned for the event. “Default” processes the standard APIs reaction, which needs no additional Callback-Signalling
phTransactionPOINTER TO BYTE
This is the Transaction State Machine (TSM) handle for the current service request. It is generated by the BACnet API and is the first parameter given to the Hook- Completion functions.
sourceAddressPOINTER TO IEC_BACNET_ADDRESS
This is the MAC address of the BACnet addressed device from which the request has been sent.
destinationAddressPOINTER TO IEC_BACNET_ADDRESS
This is the MAC address of the device constructed by the application which has received the request.
pServiceInfoPOINTER TO IEC_BACNET_PRIVATE_TRANSFER_INFO
A pointer to the service information data structure. This data structure is of data type IEC_BACNET_PRIVATE_TRANSFER_INFO.