EVT_BACNET_UNCONFEVENTNOTIFICATION (STRUCT)¶
TYPE EVT_BACNET_UNCONFEVENTNOTIFICATION : STRUCT
Receives unconfirmed Intrinsic Alarm and Event notification requests.
This is the type declaration for the Unconfirmed Event Notification service application hook. This hook allows a BACnet application to override the default processing of a Unconfirmed Event service request. This hook is given all of the parameters of a service request, and is responsible for all error checking (object existence, correspondence of parameters and any other service parameter given). A pointer to the routine is registered by BACnetSetHook. A hook can be registered at any time. One hook procedure is registered per service. If a hook is registered more than once for the same service, the new hook procedure replaces the old one. A NULL procedure pointer can be used to unregister the hook.
- InOut:
Name
Type
Comment
pCBStatusPOINTER TO IEC_BACNET_CB_STATUS
CB-Status returned for the event. “Default” processes the standard APIs reaction, which needs no additional Callback-Signalling
phTransactionPOINTER TO BYTE
This is the Transaction State Machine (TSM) handle for the current service request. It is generated by the BACnet API and is the first parameter given to the Hook- Completion functions.
sourceAddressPOINTER TO IEC_BACNET_ADDRESS
This is the MAC address of the BACnet addressed device from which the request has been sent.
destinationAddressPOINTER TO IEC_BACNET_ADDRESS
This is the MAC address of the device constructed by the application which has received the request.
pServiceInfoPOINTER TO IEC_BACNET_EVENT_NOTIF_INFO
A pointer to the service information data s tructure. This data structure is of data type BACNET_EVENT_NOTIF_INFO.