BACnetGetDeviceAddressBindingsCacheOptions (FUN)¶
FUNCTION BACnetGetDeviceAddressBindingsCacheOptions : IEC_BACNET_STATUS
Configures timing an retry parameters FOR the ‘dynamic’ address binding procedure.
This function reads the timing and retry parameters for the ‘dynamic’ address binding procedure as defined in the BACnet standard.
- InOut:
Scope
Name
Type
Comment
Return
BACnetGetDeviceAddressBindingsCacheOptionsInput
pRefreshIamCachePOINTER TO IEC_BACNET_UNSIGNED
Specifies the refresh TIME in seconds after all listed dynamic bindings get refreshed. After expiration of the refresh interval all bindings are requested using Who-Is requests again.
pWhoIsIntervalPOINTER TO IEC_BACNET_UNSIGNED
Specifies the interval in which periodically Who-Is requests are sent as long as they have not been answered and thus it is also the timeout in which an answer is expected.
pWhoIsRetriesPOINTER TO IEC_BACNET_UNSIGNED
Specifies the number OF retries made before dynamic resolution will stop until next refresh interval has expired.
pWhoIsMaxPendingPOINTER TO IEC_BACNET_UNSIGNED
Specifies the maximum number of requests with outstanding replies which might be sent out into the network.
pbPrefillCachePOINTER TO IEC_BACNET_BOOLEAN
If set to True all received I-Am requests from the network are collected even if no dynamic address resolution is requested for that device.
pbAllowUnicastIamsPOINTER TO IEC_BACNET_BOOLEAN
If set to True all received Who-Is requests are answered with unicast I am’s sent to the source address over which they have been received.