BACnetRegisterClientEventNotification (FUN)ΒΆ
FUNCTION BACnetRegisterClientEventNotification : IEC_BACNET_STATUS
Registers an device notification class reference for event and alarm acquisation.
This function enables the user appliaction to subscribe to an event and alarm source very easy. This function will do most of the work, normally a client application has to manage, just in one call. It checks periodical for the presence and online state for devices and checks for integrity of the alarms and event acquired from other devices.
- InOut:
Scope
Name
Type
Comment
Return
BACnetRegisterClientEventNotificationInput
hCustomerAn handle to an created advanced BACnet client customer created by BACnetOpenClientCustomer.
devIdThe device instance number from the remote or local device from which the events or alarms shall be acquired.
notifClassThe notification class object instance number from the remote or local device from which the events or alarms shall be acquired.
pValidTransitionsPOINTER TO IEC_BACNET_BIT_STRING
A pointer to an bit string structure which contians the bits for the transitions on which a notification shall be sent. More information can be found under BACNET_DESTINATION
pValidDaysPOINTER TO IEC_BACNET_BIT_STRING
A pointer to an bit string structure which contians the bits for the weekdays on which a notification shall be sent. More information can be found under BACNET_DESTINATION
pFromTimePOINTER TO IEC_BACNET_TIME
A pointer to a time structure which contains the start time at which notifications shall be sent. More information can be found under BACNET_DESTINATION
pToTimePOINTER TO IEC_BACNET_TIME
A pointer to a time structure which contains the end time at which notifications shall NOT be sent anymore. More information can be found under BACNET_DESTINATION
nSubscribeModeThis defines how the data is acquired.
pICallbackCmpEventMgr.ICmpEventCallbackA pointer to the event-callback interface which gets called on BACnet event notification. To unregister a NULL pointer shall be used here.
pUserArgPOINTER TO BYTE
A pointer to data from the user application which is transparent for the API. This pointer will not be modified by the BACnet API. This pointer and the pUserFct pointer is associated with the given device instance and notification class object instance pair. So for every different combination of those parameters these pointers are stored. This pointer may be NULL.