BACnetIHaveEx (FUN)ΒΆ
FUNCTION BACnetIHaveEx : IEC_BACNET_STATUS
Sends an I-Have request.
Sends a BACnet I-Have service message to a local or remote network. This routine may execute the I-Have service without using the device instance. To locate the destination it uses the destination address.
- InOut:
Scope
Name
Type
Comment
Return
BACnetIHaveExInput
pSourceAddressPOINTER TO IEC_BACNET_ADDRESS
If the BACnet application has only one device constructed and installed, this can be NULL. In this case the MAC address of this device will be used. Otherwise this shall be the MAC address returned on device object construction.
pDestinationAddressPOINTER TO IEC_BACNET_ADDRESS
This is the MAC address of the device to which the request should be sent.
pIHaveInfoPOINTER TO IEC_BACNET_I_HAVE_INFO
A pointer to the service information data structure which contains information about the source device and object - Device Instance Number, object Identifier and object Name.