BACnetGetObjectIdNameBindingsCacheOptions (FUN)¶
FUNCTION BACnetGetObjectIdNameBindingsCacheOptions : IEC_BACNET_STATUS
Configures timing an retry parameters for the ‘dynamic’ object binding procedure.
This function reads the timing and retry parameters for the ‘dynamic’ object binding procedure as defined in the BACnet standard.
- InOut:
Scope
Name
Type
Comment
Return
BACnetGetObjectIdNameBindingsCacheOptionsInput
pRefreshIhaveCachePOINTER TO IEC_BACNET_UNSIGNED
Specifies the refresh time in seconds after all listed dynamic bindings get refreshed. After expiration of the refresh interval all bindings are requested using Who-Has requests again.
pWhoHasIntervalPOINTER TO IEC_BACNET_UNSIGNED
Specifies the interval in which periodically Who-Has requests are sent as long as they have not been answered and thus it is also the timeout in which an answer is expected.
pWhoHasRetriesPOINTER TO IEC_BACNET_UNSIGNED
Specifies the number of retries made before dynamic resolution will stop until next refresh interval has expired.
pWhoHasMaxPendingPOINTER TO IEC_BACNET_UNSIGNED
Specifies the maximum number of requests with outstanding replies which might be sent out into the network.
pbPrefillCachePOINTER TO IEC_BACNET_BOOLEAN
If set to True all received I-Have requests from the network are collected even if no dynamic object identifier resolution is requested for that object name.
pbAllowUnicastIhavesPOINTER TO IEC_BACNET_BOOLEAN
If set to True all received Who-Has requests are answered with unicast I have’s sent to the source address over which they have been received.