IEC_BACNET_ACTION_COMMAND (STRUCT)ΒΆ
TYPE IEC_BACNET_ACTION_COMMAND : STRUCT
The Action-Command data structure is a specification of a single value to be written to a single property of a single object. It contains all co-ordinates of the value to be written: Device, object and Property identifiers, Array-Index and Priority (VOID if the property is not array or it is not a commandable property). This data structure also indicates a behaviour of the process of writing an optional Post-Delay attribute represents a delay in seconds prior to the execution of the next writing, Quit-On-Failure flag indicates if the device shall terminate the execution of the action list prematurely in the case of writing fail (TRUE) or writing shall continue after each failure with the next element of the action list. A Write-Successful attribute of Action-Command data structure shall be set to FALSE if the write fails for any reason. If the Quit-On-Failure attribute of Action-Command data structure is TRUE and the write fails, then it terminate the execution list prematurely and set Write-Successful flag in subsequent entries in the same list to FALSE.
- InOut:
Name
Type
Comment
maskFlags which indicate what parameters are present and valid.
Combined valid values are: ACTION_DEVICE_ID_FLAG or ACTION_POST_DELAY_FLAG.
deviceIDAn optional BACnet device identifier which is referenced.
objectIDAn object identifier which is referenced.
propertyIDThe property identifier which is referenced.
indexThe optional property array index.
Ihis is used only with array datatypes. For referencing non array datatypes BACNET_VOID_INDEX (-1) shall be used.
valueA value to be written.
priorityA conditional priority.
postDelayAn optional post-writing delay time.
quitOnFailureA premature quit flag.
writeSuccessfulA write success flag.