BACnetWritePropertyMultiple (FUN)¶
FUNCTION BACnetWritePropertyMultiple : IEC_BACNET_STATUS
Sends an WritePropertyMultiple request.
Modifies the values of one or more specified properties of one or more Objects. This routine may control APDU properties like APDU length, segmentation, and timeout for both request and in response. This routine can execute asynchronously, i.e. this routine will return to the caller before the BACnet reply comes so that the application can keep running. In this case the response information will be received by the thread which is responsible for receiving asynchronous responses. An optional BACNET_WRITE_PROP_MUL_COMPLETE_CB routine, which is provided by the application, shall be used to process this information. If a number of asynchronous requests are sent, the responses shall be queued and identified by the transaction handles. If the application does not supply the BACNET_WRITE_PROP_MUL_COMPLETE_CB routine then this routine sends a request and waits for the reply.
Asynchron call. As soon as pResultStatus is IEC_BACNET_STATUS.BACNET_STATUS_OK the call was successfully completed.
- InOut:
Scope
Name
Type
Comment
Return
BACnetWritePropertyMultipleA status indicating whether the operation worked.
Input
pSourceAddressPOINTER TO IEC_BACNET_ADDRESS
If the BACnet application has only one device constructed and installed, this can be 0. In this case the MAC address of this device will be used. Otherwise this shall be the MAC address returned on device object construction.
pDestinationAddressPOINTER TO IEC_BACNET_ADDRESS
This is the MAC address of the device to which the request should be sent.
pServiceInfoPOINTER TO IEC_BACNET_WRITE_MUL_INFO
A pointer to the service request information data structure.
pAPDUParamsPOINTER TO IEC_BACNET_APDU_PROPERTIES
A pointer to the APDU-Properties structure which sets APDU properties for this transaction only. This does not change global defaults or settings for the application APDU Properties. This argument may be 0. In this case APDU properties are used which were specified in the device object properties of the applications device which sends the request.
pTransactionTokenPOINTER TO BACnetAsyncTransactionToken
Transaction token of the asynchronous call - see BACnetAsyncTransactionToken.
pErrorPOINTER TO IEC_BACNET_ERROR
A pointer to a structure to hold BACnet Error information. pError may be 0 if the application isn’t interested in detailed error information.
pFirstFailedPOINTER TO IEC_BACNET_DEV_OBJ_PROP_REFERENCE
A pointer to a structure to hold the device object property refernce which failed to be written.