EVT_BACNET_DCC (STRUCT)¶
TYPE EVT_BACNET_DCC : STRUCT
The DeviceCommunicationControl service hook
This is the type declaration for the Device-Communication-Control service application hook. This hook allows a BACnet application to override the default processing of a Device-Communication-Control service request. This hook is given all of the parameters of a service request, and is responsible for all error checking (Device existence, parameter correctness and so forth). A pointer to the routine is registered with the BACnet server by BACnetSetHook. A hook can be registered by the registering API routine at any time. One hook procedure is registered per service. If a hook is registered more than once for the same service, the new hook procedure replaces old one. A 0 procedure pointer can be used to deregister the hook. A Device-Communication-Control hook must complete its service request processing by using one of the transaction completion API routines: BACnetSrvcResponseCbCompletion, BACnetSrvcAbortCbCompletion, BACnetSrvcErrorCbCompletion, BACnetSrvcIgnoreCbCompletion, or BACnetSrvcRejectCbCompletion. Hooks can access the local Properties maintained in the API database by using the BACnetStorePropertyInstance / BACnetRetrievePropertyInstance routines. A hook can choose not to override the default API processing of a service request by returning the value CB_STATUS_DEFAULT.
- InOut:
Name
Type
Comment
pCBStatusPOINTER TO IEC_BACNET_CB_STATUS
CB-Status returned for the event. “Default” processes the standard APIs reaction, which needs no additional Callback-Signalling.
phTransactionPOINTER TO BYTE
This is the Transaction State Machine (TSM) handle for the current service request. It is generated by the BACnet API and is the first parameter given to the Hook- Completion functions.
sourceAddressPOINTER TO IEC_BACNET_ADDRESS
This is the MAC address of the BACnet addressed device from which the request has been sent.
destinationAddressPOINTER TO IEC_BACNET_ADDRESS
This is the MAC address of the device constructed by the application which has received the request.
pServiceInfoPOINTER TO IEC_BACNET_DCC_INFO
A pointer to the service information data structure. The fields of this data structure include the time duration which may be indefinite or indicate a number of minutes during which the remote device shall ignore all APDUs except Device-Communication-Control and Reinitialize-Device APDUs, dccValue which may be DCC_ENABLE, DCC_DISABLE, or DCC_DISABLE_INITIATION, and a password.