BACnetSetDccValue (FUN)ΒΆ
FUNCTION BACnetSetDccValue : IEC_BACNET_STATUS
Sets the device communication control status of a local device.
Sets a value of the Device Communication Control Value (DCC-Value). This value indicates whether or not a device is able to initiate and respond to APDUs on the communication internetwork, depending on whether the DCC-Value is DCC_ENABLE or DCC_DISABLE or DCC_DISABLE_INITIATION. This routine instructs the Server or Gateway application to either disable or enable initiating and responding APDUs. The default value of DCC-Value is DCC_ENABLE. This routine sets the DCC-Value in one Server / Gateway application.
- InOut:
Scope
Name
Type
Comment
Return
BACnetSetDccValueA status indicating if the operation worked.
Input
instNumberThe Device Object instance number of the Device.
valueThe device communication value to set for the specified device.