EVT_BACNET_INTRINSICEVENTS (STRUCT)¶
TYPE EVT_BACNET_INTRINSICEVENTS : STRUCT
Callback to give user access to BACnet server API internal generated intrinsic event notifications.
An application may register a callback for internal generated intrinsic notifications by a call to BACnetSetHook. This callback will be called every time that an intrinsic notification is generated by some API internal process.
- InOut:
Name
Type
Comment
pCBStatusPOINTER TO IEC_BACNET_CB_STATUS
CB-Status returned for the event. “Default” processes the standard APIs reaction, which needs no additional Callback-Signalling. The application can suppress the sending by returning an other value than CB_STATUS_OK.
pEventInfoPOINTER TO IEC_BACNET_EVENT_NOTIF_INFO
A pointer to a structure which contains all information for the intrinsic event notification to be sent.