BACnetRemoveListElement (FUN)¶
FUNCTION BACnetRemoveListElement : IEC_BACNET_STATUS
Sends an Remove-List-Element request
Sends a request to remove one or more list elements from an object property which is a list. This routine may control APDU properties like APDU length, segmentation, and timeout for both request and in response. This routine can execute asynchronously, i.e. this routine will return to the caller before the BACnet reply comes so that the applications can keep running. In this case the response information will be received by the thread which is responsible for receiving asynchronous responses. An optional BACNET_CHANGE_LIST_COMPLETE_CB routine, which is provided by the BACnet application, shall be used to process this information. If a number of asynchronous requests are sent, the responses shall be queued and identified by the transaction handles. If the application does not supply the BACNET_CHANGE_LIST_COMPLETE_CB routine then the BACnetRemoveListElement routine sends a request and waits for the reply.
- InOut:
Scope
Name
Type
Comment
Return
BACnetRemoveListElementA status indicating whether the operation worked.
Input
pSourceAddressPOINTER TO IEC_BACNET_ADDRESS
If the BACnet application has only one device constructed and installed, this can be 0. In this case the MAC address of this device will be used. Otherwise this shall be the MAC address returned on device object construction.
pDestinationAddressPOINTER TO IEC_BACNET_ADDRESS
This is the MAC address of the device to which the request should be sent.
pRemoveInfoPOINTER TO IEC_BACNET_CHANGE_LIST_INFO
A pointer to the service information data structure. This data structure contains the objectID, ePropertyID, nIndex and a buffer in which the Property Contents datatype list is placed.
pAPDUParamsPOINTER TO IEC_BACNET_APDU_PROPERTIES
A pointer to the APDU-Properties structure which sets APDU properties for this transaction only. This does not change global defaults or settings for the application APDU Properties. This argument may be 0. In this case APDU properties are used which were specified in the device object properties of the applications device which sends the request.
pTransactionTokenPOINTER TO BACnetAsyncTransactionToken
Transaction token of the asynchronous call - see BACnetAsyncTransactionToken.
pErrorPOINTER TO IEC_BACNET_ERROR
A pointer to a structure to hold BACnet Error information. pError may be 0 if the application isn’t interested in detailed error information.
pFirstFailedPOINTER TO IEC_BACNET_UNSIGNED
A pointer to a buffer in which to place the sequence number of the first element in the pElements list which cannot be added to the property. pFirstFailed may be 0.