BACnetCommand.InitializeActionCommandBACnetBoolean (METH)ΒΆ
METHOD InitializeActionCommandBACnetBoolean
Initialized a BACnet-ActionCommand, which writes a BACnet-Boolean value to another BACnet-Object-Property. The initialized command then normally is used as part of a BACnet-ActionList.
- InOut:
- Scope - Name - Type - Comment - Input - devInst- CmpBACnet.IEC_BACNET_DWORD- The instance number of the targeted BACnet device. - bacObjectInst- CmpBACnet.IEC_BACNET_DWORD- The instance number of the targeted BACnet object under the BACnet device. - bacObjectType- CmpBACnet.IEC_BACNET_OBJECT_TYPE- The type of the targeted BACnet object under the BACnet device. - bacPropertyID- CmpBACnet.IEC_BACNET_PROPERTY_ID- The property ID of the targetedn property under the BACnet object. - priority- CmpBACnet.IEC_BACNET_SIGNED- The priority used to write the BinaryPV value to the targeted property. - postDelay- CmpBACnet.IEC_BACNET_UNSIGNED- The post delay after writing the BinaryPV value. - quitOnFailure- CmpBACnet.IEC_BACNET_BOOLEAN- Whether the action list execution shall be quited on failure of this action command or not. - Inout - bacBoolean- CmpBACnet.IEC_BACNET_BOOLEAN- The boolean value to be written. - bacActionCommand- CmpBACnet.IEC_BACNET_ACTION_COMMAND- The action command structure to be filled. 
