BACnetClientRemoveListElement (FB)¶
FUNCTION_BLOCK PUBLIC FINAL BACnetClientRemoveListElement EXTENDS BACnetClientBase
Common Behaviour Model conform (ETrigA) FB to execute a Remove-List-Element-Request in the BACnet-Network. If execution completed successfully and xDone is TRUE, the Remove-List-Element-Request was successful. In any other case eStatus and errorResult may hold additional information of what failed and firstFailed holds the index of the first element, which failed to be removed.
- InOut:
- Scope - Name - Type - Initial - Comment - Inherited from - Input - xExecute- BOOLRising edge: Starts defined operation- FALSE: Resets the defined operation after ready condition was reached- ETrigATo - xAbort- BOOL- TRUE: Aborts the operation- ETrigATo - udiTimeOut- UDINT- Max. operating time for executing [µs], 0: No operating time limit - ETrigATo - Output - xDone- BOOL- TRUE: Ready condition reached- ETrigATo - xBusy- BOOL- TRUE: Operation is running- ETrigATo - xError- BOOL- TRUE: Error condition reached- ETrigATo - xAborted- BOOL- TRUE: Abort condition reached- ETrigATo - Input - dwTargetDeviceNumber- DWORD- The device number of the targeted device in the BACnet- Network. - pTargetDeviceAddress- POINTER TO CmpBACnet.IEC_BACNET_ADDRESS - 0 - Optional: The device address of the targeted device in the BACnet-Network. If an adress is given the given device number is ignored. - Output - eStatus- CmpBACnet.IEC_BACNET_STATUS- CmpBACnet.IEC_BACNET_STATUS.BACNET_STATUS_OK - If an error occured, the error state. - errorResult- CmpBACnet.IEC_BACNET_ERROR- STRUCT(tag := CmpBACnet.IEC_BACNET_FAILURE_TYPE._FAILURE_MAX_SIZE) - If an error occured (this means eStatus <> BACNET_STATUS_OK), whereas the sent BACnet-Request was answered with an specific error information, the latter is contained in this structure. - iState- DINT- 0 - The State in which the FB is during execution:
- 0: No execution, resetted state 
- 1: Searching for the Target-Device and a valid address for it 
- 2: Sending the BACnet-Request into the network 
- 3: Waiting for the answer (if there is one) to the BACnet-Request made in 2 
- 4: Finishing the call, setting of the output variables 
 
 - Input - objType- CmpBACnet.IEC_BACNET_OBJECT_TYPE- The type of the object under the targeted device to remove a list element from. - objInst- CmpBACnet.IEC_BACNET_DWORD- The instance number of the object under the targeted device to remove a list element from. - propID- CmpBACnet.IEC_BACNET_PROPERTY_ID- The property ID of the property of the object under the targeted device to remove a list element from. - nIndex- CmpBACnet.IEC_BACNET_SIGNED- The Index of the element in the property, where the elements of property Contents shall be removed. - elements- CmpBACnet.IEC_BACNET_PROPERTY_CONTENTS- The elements to be removed from the property (compare elements.nElements). - Output - firstFailed- CmpBACnet.IEC_BACNET_UNSIGNED- If the Remove-List-Element-Request failed, this variable holds the index of the first element, which failed to be removed. 
Properties:
Instance, inherited from BACnetClientBase
Running, inherited from BACnetClientBase
Server, inherited from BACnetClientBase
SourceDeviceAddress, inherited from BACnetClientBase
SourceDeviceNumber, inherited from BACnetClientBase
TargetDeviceAddress, inherited from BACnetClientBase
TargetDeviceNumber, inherited from BACnetClientBase
Methods:
RegisterToServer, inherited from BACnetClientBase
UnregisterFromServer, inherited from BACnetClientBase
Structure:
