BACnetClientCreateObject (FB)¶
FUNCTION_BLOCK PUBLIC FINAL BACnetClientCreateObject EXTENDS BACnetClientBase
Common Behaviour Model conform (ETrigA) FB to execute a Create-Object-Reqeust in the BACnet-Network. If execution completed successfully and xDone is TRUE,CreateObjectID holds mthe ID of the created object. If the request fails, firstFailed holds the index of the first property, due to which reason the creation failed.
- InOut:
- Scope - Name - Type - Initial - Comment - Inherited from - Input - xExecute- BOOLRising edge: Starts defined operation- FALSE: Resets the defined operation after ready condition was reached- ETrigATo - xAbort- BOOL- TRUE: Aborts the operation- ETrigATo - udiTimeOut- UDINT- Max. operating time for executing [µs], 0: No operating time limit - ETrigATo - Output - xDone- BOOL- TRUE: Ready condition reached- ETrigATo - xBusy- BOOL- TRUE: Operation is running- ETrigATo - xError- BOOL- TRUE: Error condition reached- ETrigATo - xAborted- BOOL- TRUE: Abort condition reached- ETrigATo - Input - dwTargetDeviceNumber- DWORD- The device number of the targeted device in the BACnet- Network. - pTargetDeviceAddress- POINTER TO CmpBACnet.IEC_BACNET_ADDRESS - 0 - Optional: The device address of the targeted device in the BACnet-Network. If an adress is given the given device number is ignored. - Output - eStatus- CmpBACnet.IEC_BACNET_STATUS- CmpBACnet.IEC_BACNET_STATUS.BACNET_STATUS_OK - If an error occured, the error state. - errorResult- CmpBACnet.IEC_BACNET_ERROR- STRUCT(tag := CmpBACnet.IEC_BACNET_FAILURE_TYPE._FAILURE_MAX_SIZE) - If an error occured (this means eStatus <> BACNET_STATUS_OK), whereas the sent BACnet-Request was answered with an specific error information, the latter is contained in this structure. - iState- DINT- 0 - The State in which the FB is during execution:
- 0: No execution, resetted state 
- 1: Searching for the Target-Device and a valid address for it 
- 2: Sending the BACnet-Request into the network 
- 3: Waiting for the answer (if there is one) to the BACnet-Request made in 2 
- 4: Finishing the call, setting of the output variables 
 
 - Input - objectSpecifier- CmpBACnet.IEC_BACNET_OBJECT_SPECIFIER- This parameter contains information about the type of object that is to be created. The datatype is a choice between an object type and an object identifier. If the object type choice is used, the specified object type shall become the value of the Object_Type property of the newly created object and the responding BACnet-user shall select an object identifier. If the object identifier choice is used, an object with this particular object identifier shall be created. - bValuesPresent- BOOL- TRUE - If set to True the list of initial values is valid. - nValuesCount- CmpBACnet.IEC_BACNET_UNSIGNED- Number of entries in the list of initial values. - pValues- POINTER TO CmpBACnet.IEC_BACNET_PROPERTY_VALUE - This parameter contains a list of BACnetPropertyValues that will be used to initialize the values of the specified properties of the newly created object. - Output - createdObjectID- CmpBACnet.IEC_BACNET_OBJECT_ID- If the BACnet-Request succeeded (xDone is TRUE and no error occured (xError is FALSE)), this variable holds the object ID of the created object. - firstFailed- CmpBACnet.IEC_BACNET_UNSIGNED- If the BACnet-Request failed, this variable shall hold the first property, for which the creation of the object failed. 
Properties:
Instance, inherited from BACnetClientBase
Running, inherited from BACnetClientBase
Server, inherited from BACnetClientBase
SourceDeviceAddress, inherited from BACnetClientBase
SourceDeviceNumber, inherited from BACnetClientBase
TargetDeviceAddress, inherited from BACnetClientBase
TargetDeviceNumber, inherited from BACnetClientBase
Methods:
RegisterToServer, inherited from BACnetClientBase
UnregisterFromServer, inherited from BACnetClientBase
Structure: