BACnetDateTime (STRUCT)¶
TYPE BACnetDateTime : STRUCT
Helper Structure for CODESYS-typed date times to work with BACnet properties of BACnet standard type “BACnetDateTime” represented by CmpBACnet.IEC_BACNET_DATE_TIME.
Please note: CmpBACnet.IEC_BACNET_DATE_TIME allows “unspecified” elements, but BACnetDateTime does not for historic reason.
CmpBACnet.IEC_BACNET_DATE_TIME allows “unspecified” elements which are used for two different objectives. 1.) eventually “fully unspecified”: properties representing a time stamp or a time range start / end, for example BinaryInput.Change_Of_State_Time or TrendLog.Start_Time / .Stop_Time 2.) eventually “partially unspecified”: Schedule.Exception_Schedule The BACnet standard uses the terms “fully unspecified” or “fully specified”, but not the term “partially unspecified” (instead a bit more unspecific “unspecified”).
“fully unspecified”: In most cases a time stamp indicates the time of a change of object state. Prior to first change of object state the time stamp is supposed to be “unspecified”. For an example see File.Modification_Date or PulseConverter.Update_Time Another use case of “fully unspecified” is a time range - see TrendLog.Start_Time and .Stop_Time or Schedule.
“partially unspecified” is mainly used in Schedule.Exception_Schedule
BACnetDateTime has been used in earlier versions of CODESYS BACnet as an API type instead of CmpBACnet.IEC_BACNET_DATE_TIME for convenience. So an interface breaking change would have been necessary to switch to CmpBACnet.IEC_BACNET_DATE_TIME to allow “unspecified” directly. We found this too hard of a measure, so we kept BACnetDateTime as an API type and added some assumptions and helper functions.
Assumption: a BACnetDateTime dat = D#1970-1-1 AND tim = T#0S (begin of universe) or dat = D#2106-2-7 AND tim = T#23H59M59S999MS (end of universe) is assumed to be “fully unspecified”.
Helper functions: IsBACnetBACnetDateTimeUnspecified to check if a BACnetDateTime is “fully unspecified”. IsBACnetDateTimeUnspecified to check if a CmpBACnet.IEC_BACNET_DATE_TIME is “fully unspecified”. InitializeBACnetDateTimeUnspecified to initialize a CmpBACnet.IEC_BACNET_DATE_TIME to “fully unspecified”. BACnetObjectBase.SetBACnetDateTimePropertyToUnspecified to initialize a property to “fully unspecified”.
- InOut:
- Name - Type - dat- DATE- tim- TIME