BACnetClientSubscribeCOV (FB)¶
FUNCTION_BLOCK PUBLIC FINAL BACnetClientSubscribeCOV EXTENDS BACnetClientBase
Common Behaviour Model conform (ETrigA) FB to execute a Subscribe-COV-Request in the BACnet-Network. If execution completed successfully and xDone is TRUE, the COV-Subscription was successful. In any other case eStatus and errorResult may hold additional information of what failed.
- InOut:
- Scope - Name - Type - Initial - Comment - Inherited from - Input - xExecute- BOOLRising edge: Starts defined operation- FALSE: Resets the defined operation after ready condition was reached- ETrigATo - xAbort- BOOL- TRUE: Aborts the operation- ETrigATo - udiTimeOut- UDINT- Max. operating time for executing [µs], 0: No operating time limit - ETrigATo - Output - xDone- BOOL- TRUE: Ready condition reached- ETrigATo - xBusy- BOOL- TRUE: Operation is running- ETrigATo - xError- BOOL- TRUE: Error condition reached- ETrigATo - xAborted- BOOL- TRUE: Abort condition reached- ETrigATo - Input - dwTargetDeviceNumber- DWORD- The device number of the targeted device in the BACnet- Network. - pTargetDeviceAddress- POINTER TO CmpBACnet.IEC_BACNET_ADDRESS - 0 - Optional: The device address of the targeted device in the BACnet-Network. If an adress is given the given device number is ignored. - Output - eStatus- CmpBACnet.IEC_BACNET_STATUS- CmpBACnet.IEC_BACNET_STATUS.BACNET_STATUS_OK - If an error occured, the error state. - errorResult- CmpBACnet.IEC_BACNET_ERROR- STRUCT(tag := CmpBACnet.IEC_BACNET_FAILURE_TYPE._FAILURE_MAX_SIZE) - If an error occured (this means eStatus <> BACNET_STATUS_OK), whereas the sent BACnet-Request was answered with an specific error information, the latter is contained in this structure. - iState- DINT- 0 - The State in which the FB is during execution:
- 0: No execution, resetted state 
- 1: Searching for the Target-Device and a valid address for it 
- 2: Sending the BACnet-Request into the network 
- 3: Waiting for the answer (if there is one) to the BACnet-Request made in 2 
- 4: Finishing the call, setting of the output variables 
 
 - Input - xSubscribe- BOOL- TRUE - Describes whether the COV subsciption shall be made/renewed or deleted. - xIssueConfirmedNotifications- BOOL- Describes whether confirmed or unconfirmed COV notification shall be send by the COV-Provider. - monitoredObjType- CmpBACnet.IEC_BACNET_OBJECT_TYPE- Object type of the monitored object under the targeted device. - monitoredObjInst- CmpBACnet.IEC_BACNET_DWORD- Object instance of the monitored object under the targeted device. - lifetime- CmpBACnet.IEC_BACNET_UNSIGNED- Lifetime of the COV-Subscription in seconds. Use 0 for infinite lifetime. 
Properties:
Instance, inherited from BACnetClientBase
Running, inherited from BACnetClientBase
Server, inherited from BACnetClientBase
SourceDeviceAddress, inherited from BACnetClientBase
SourceDeviceNumber, inherited from BACnetClientBase
TargetDeviceAddress, inherited from BACnetClientBase
TargetDeviceNumber, inherited from BACnetClientBase
Methods:
InitializeOutputs, inherited from BACnetClientBase
RegisterToServer, inherited from BACnetClientBase
UnregisterFromServer, inherited from BACnetClientBase
Structure:
