BACnetClientReadRange (FB)¶
FUNCTION_BLOCK PUBLIC FINAL BACnetClientReadRange EXTENDS BACnetClientBase
Common Behaviour Model conform (ETrigA) FB to execute a Read-Range-Reqeust in the BACnet-Network. Ifexecution completed successfully and xDone is TRUE, result is filled with valid data, in any other case the data in result are not valid.
- InOut:
- Scope - Name - Type - Initial - Comment - Inherited from - Input - xExecute- BOOLRising edge: Starts defined operation- FALSE: Resets the defined operation after ready condition was reached- ETrigATo - xAbort- BOOL- TRUE: Aborts the operation- ETrigATo - udiTimeOut- UDINT- Max. operating time for executing [µs], 0: No operating time limit - ETrigATo - Output - xDone- BOOL- TRUE: Ready condition reached- ETrigATo - xBusy- BOOL- TRUE: Operation is running- ETrigATo - xError- BOOL- TRUE: Error condition reached- ETrigATo - xAborted- BOOL- TRUE: Abort condition reached- ETrigATo - Input - dwTargetDeviceNumber- DWORD- The device number of the targeted device in the BACnet- Network. - pTargetDeviceAddress- POINTER TO CmpBACnet.IEC_BACNET_ADDRESS - 0 - Optional: The device address of the targeted device in the BACnet-Network. If an adress is given the given device number is ignored. - Output - eStatus- CmpBACnet.IEC_BACNET_STATUS- CmpBACnet.IEC_BACNET_STATUS.BACNET_STATUS_OK - If an error occured, the error state. - errorResult- CmpBACnet.IEC_BACNET_ERROR- STRUCT(tag := CmpBACnet.IEC_BACNET_FAILURE_TYPE._FAILURE_MAX_SIZE) - If an error occured (this means eStatus <> BACNET_STATUS_OK), whereas the sent BACnet-Request was answered with an specific error information, the latter is contained in this structure. - iState- DINT- 0 - The State in which the FB is during execution:
- 0: No execution, resetted state 
- 1: Searching for the Target-Device and a valid address for it 
- 2: Sending the BACnet-Request into the network 
- 3: Waiting for the answer (if there is one) to the BACnet-Request made in 2 
- 4: Finishing the call, setting of the output variables 
 
 - Input - objType- CmpBACnet.IEC_BACNET_OBJECT_TYPE- The type of the object under the targeted device to read the range from. - objInst- CmpBACnet.IEC_BACNET_DWORD- The instance number of the object under the targeted device to read the range from. - propID- CmpBACnet.IEC_BACNET_PROPERTY_ID- The property ID of the property of the object under the targeted device to read the range from. - rangeType- CmpBACnet.IEC_BACNET_RANGE_TYPE- The type of the range to be read. - range- CmpBACnet.IEC_BACNET_READ_RANGE_RANGE- The type dependant range to be read. - nIndex- CmpBACnet.IEC_BACNET_SIGNED- -1 - Optional: The Index of the element of the property read. Only use for constant array properties. Otherwise use index -1 or leave empty. - Output - result- CmpBACnet.IEC_BACNET_READ_RANGE_RESULT- If the BACnet-Request succeeded (xDone is TRUE and no error occured (xError is FALSE)), this variable holds the contents of the read property. Use the helper functions GetRealFromContents, Get… to evaluate its value (for simple property types). Otherwise be sure to correctly interpretate the contents data. 
Properties:
Instance, inherited from BACnetClientBase
Running, inherited from BACnetClientBase
Server, inherited from BACnetClientBase
SourceDeviceAddress, inherited from BACnetClientBase
SourceDeviceNumber, inherited from BACnetClientBase
TargetDeviceAddress, inherited from BACnetClientBase
TargetDeviceNumber, inherited from BACnetClientBase
Methods:
RegisterToServer, inherited from BACnetClientBase
UnregisterFromServer, inherited from BACnetClientBase
Structure:
