BACnetClientLifeSafetyOperation (FB)¶
FUNCTION_BLOCK PUBLIC FINAL BACnetClientLifeSafetyOperation EXTENDS BACnetClientBase
Common Behaviour Model conform (ETrigA) FB to send a LifeSafetyOperation-Request in the BACnet-Network. If execution completed successfully and xDone is TRUE, the request was successful. In any other case eStatus and errorResult may hold additional information of what failed.
- InOut:
- Scope - Name - Type - Initial - Comment - Inherited from - Input - xExecute- BOOLRising edge: Starts defined operation- FALSE: Resets the defined operation after ready condition was reached- ETrigATo - xAbort- BOOL- TRUE: Aborts the operation- ETrigATo - udiTimeOut- UDINT- Max. operating time for executing [µs], 0: No operating time limit - ETrigATo - Output - xDone- BOOL- TRUE: Ready condition reached- ETrigATo - xBusy- BOOL- TRUE: Operation is running- ETrigATo - xError- BOOL- TRUE: Error condition reached- ETrigATo - xAborted- BOOL- TRUE: Abort condition reached- ETrigATo - Input - dwTargetDeviceNumber- DWORD- The device number of the targeted device in the BACnet- Network. - pTargetDeviceAddress- POINTER TO CmpBACnet.IEC_BACNET_ADDRESS - 0 - Optional: The device address of the targeted device in the BACnet-Network. If an adress is given the given device number is ignored. - Output - eStatus- CmpBACnet.IEC_BACNET_STATUS- CmpBACnet.IEC_BACNET_STATUS.BACNET_STATUS_OK - If an error occured, the error state. - errorResult- CmpBACnet.IEC_BACNET_ERROR- STRUCT(tag := CmpBACnet.IEC_BACNET_FAILURE_TYPE._FAILURE_MAX_SIZE) - If an error occured (this means eStatus <> BACNET_STATUS_OK), whereas the sent BACnet-Request was answered with an specific error information, the latter is contained in this structure. - iState- DINT- 0 - The State in which the FB is during execution:
- 0: No execution, resetted state 
- 1: Searching for the Target-Device and a valid address for it 
- 2: Sending the BACnet-Request into the network 
- 3: Waiting for the answer (if there is one) to the BACnet-Request made in 2 
- 4: Finishing the call, setting of the output variables 
 
 - Input - fSafetyObjectIdPresent- CmpBACnet.IEC_BACNET_BOOLEAN- If set to true the objectID parameter is valid and present. - processID- CmpBACnet.IEC_BACNET_UNSIGNED- The processID attribute is the numeric identifier of the Process within the client which shall receive the notifications. - requestingSource- CmpBACnet.IEC_BACNET_STRING- This attribute specifies the identity of the human operator that initiates this service request. - eRequest- CmpBACnet.IEC_BACNET_LIFE_SAFETY_OPERATION- This attribute specifies the requested operation (which may take on one of the standard values: NONE, SILENCE, SILENCE_AUDIBLE, SILENCE_VISUAL, RESET, RESET_ALARM, RESET_FAULT). - objectID- CmpBACnet.IEC_BACNET_OBJECT_ID- The object ID attribute is optional. If it is omitted the request is interpreted as an operation on all applicable objects within the receiving device. The mask attribute indicates if the object ID is present. 
Properties:
Instance, inherited from BACnetClientBase
Running, inherited from BACnetClientBase
Server, inherited from BACnetClientBase
SourceDeviceAddress, inherited from BACnetClientBase
SourceDeviceNumber, inherited from BACnetClientBase
TargetDeviceAddress, inherited from BACnetClientBase
TargetDeviceNumber, inherited from BACnetClientBase
Methods:
InitializeOutputs, inherited from BACnetClientBase
RegisterToServer, inherited from BACnetClientBase
UnregisterFromServer, inherited from BACnetClientBase
Structure: