UNION_BACNET_STACK_CONTROL (UNION)ΒΆ

TYPE UNION_BACNET_STACK_CONTROL : UNION

Structure for different stack API control command definitions.

InOut:

Name

Type

Comment

readWriteBdt

IEC_BACNET_BVLL_WRITE_BDT

Command data for reading and writing broadcast distribution tables.

readWriteFdt

IEC_BACNET_BVLL_READ_FDT

Command data for reading and writing foreign device tables.

statisticData

IEC_BACNET_CONTROL_STATS

Command data returned on statistic command.

rangeChecking

IEC_BACNET_CONTROL_RANGECHK

Command data for configuring the range check capabillity in the stack.

newMacAddress

IEC_BACNET_ADDRESS

Command data for changing datalink bound MAC address for MS/TP and IP at runtime.

bdtEntry

IEC_BACNET_CONTROL_BDT_ENTRY

BDT table entry.

fdtEntry

IEC_BACNET_CONTROL_FDT_ENTRY

FDT table entry.

vmacEntry

IEC_BACNET_CONTROL_VMAC_ENTRY

VMAC table entry.

routerEntry

IEC_BACNET_CONTROL_ROUTER_ENTRY

BACnet router table entry.

configPathFile

ARRAY [0..511] OF IEC_BACNET_BYTE

For setting and getting the configuration path and file for deamon process.

dlinkStatus

IEC_BACNET_DATALINK_EVENT

The current status of the requested datalink.