IEC_BACNET_DUMP_REPORT_FLAGS (ENUM)

TYPE IEC_BACNET_DUMP_REPORT_FLAGS :

Defined flags for controlling and filtering the output of the dump function.

InOut:

Name

Initial

Comment

BACNET_DUMP_REPORT_BAD_COV_STATE

16#1

Flag controls output of bad COV recipients in the server API database.

If set the dump will list out bad COV recipients. Bad COV recipients are recipients which have subscribed to objects and which should have received notifications but haven’t acknowledged them.

BACNET_DUMP_REPORT_BAD_INT_STATE

16#2

Flag controls output of bad intrinsic recipients in the server API database.

If set the dump will list out bad intrinsic recipients. Bad intrinsic recipients are recipients which have subscribed to objects and which should have received notifications but haven’t acknowledged them.

BACNET_DUMP_REPORT_OBJECT_INT_STATE

16#4

Flag controls output of intrinsic recipients in the server API database which have registered to some notification-class objects.

If set the dump will contain intrinsic recipient entries registered to notification class objects in the server API database.

BACNET_DUMP_REPORT_OBJECT_COV_STATE

16#8

Flag controls output of COV recipients in the server API database which have registered to some objects.

If set the dump will contain COV and COVP recipient entries registered to objects in the server API database.

BACNET_DUMP_REPORT_ROUTER_STATE

16#10

Flag controls output of the router state in the network layer.

16#20

Flag controls output of the configured datalinks in the network layer.

BACNET_DUMP_REPORT_ADDRESS_RESOLUTION

16#40

Flag controls output of the pending dynamic address bindings.

BACNET_DUMP_REPORT_NAME_RESOLUTION

16#80

Flag controls output of the dynamic object identifier binding.

BACNET_DUMP_REPORT_CLNT_DATABASE

16#100

Flag controls output of the advanced client API registered objects and events.