IEC_BACNET_NMM_ERROR_ROUTER_CFG (STRUCT)ΒΆ

TYPE IEC_BACNET_NMM_ERROR_ROUTER_CFG : STRUCT

Structure containing information about the router conflict. With the who-is-router and i-am-router service a device may request a routing path to a device which lies behind a router. In BACnet it is defined that only ONE router to a network may exist. In case there are multiple replies from different sources this event will be issued.

InOut:

Name

Type

Comment

netnumber

IEC_BACNET_WORD

The network number in question.

activeRouter

IEC_BACNET_ADDRESS

The actual, first assigned router address to the network above.

conflictingRouter

IEC_BACNET_ADDRESS

The router address which also reports to be a router to the network above.