IEC_BACNET_AUTHENTICATION_POLICY (STRUCT)ΒΆ

TYPE IEC_BACNET_AUTHENTICATION_POLICY : STRUCT

Definition of the BACnetAuthenticationPolicy structure

This structuee specifies the authentication policies defined for an Access Point object.

InOut:

Name

Type

Comment

nPolicyCount

IEC_BACNET_ELEMENT_COUNT

Count of entries in the List_Of_Policies

policies

POINTER TO IEC_BACNET_AUTHENTICATION_POLICY_DATAINPUT

This field is a list of sequence elements that specifies the Credential Data Input objects which are used for this authentication policy

fOrderEnforced

IEC_BACNET_BOOLEAN

If TRUE, then the ordering sequence, as specified by the Index fields of this Policy list, is enforced. If FALSE, then the order is not enforced.

nTimeout

IEC_BACNET_UINT

This field, of type Unsigned, specifies the maximum time in seconds for which all authentication factors, as defined by this policy, must be presented. A value of zero indicates an unlimited time to present all authentication factors. If not all authentication factors are presented in the allotted time, then a timeout occurs and authentication fails.