IEC_BACNET_AUTHENTICATION_FACTOR_FORMAT (STRUCT)ΒΆ

TYPE IEC_BACNET_AUTHENTICATION_FACTOR_FORMAT : STRUCT

Definition of the BACnetAuthenticationFactorFormat structure

This structure, of type BACnetAuthenticationFactorFormat, is used to specify which authentication factor formats are supported by this object.

InOut:

Name

Type

Comment

formatType

IEC_BACNET_AUTHENTICATION_FACTOR_TYPE

This field, of type BACnetAuthenticationFactorType, specifies a supported authentication factor format type.

fVendorIdPresent

IEC_BACNET_BOOLEAN

If set to True the vendor identifier is valid

vendorId

IEC_BACNET_WORD

This optional field, of type Unsigned, is required when Format-Type field has a value of CUSTOM. It shall contain the BACnet vendor identifier of the vendor which defined the custom format. This value may differ from the Vendor_Identifier property value in the Device object, which identifies the device manufacturer. If the Format-Type field does not have a value of CUSTOM and this field is present it shall have a value of zero.

fVendorFormatPresent

IEC_BACNET_BOOLEAN

If set to True the vendor format is valid

vendorFormat

IEC_BACNET_WORD

This optional field of type Unsigned is required when Format-Type field has a value of CUSTOM. It shall contain a unique identifier that identifies a specific custom authentication factor format as defined by the BACnet vendor in the Vendor-ID field. If the Format-Type field does not have a value of CUSTOM and this field is present, then it shall have a value of zero.