EVT_BACNET_UNCONF_PRIVATE_XFER (STRUCT)¶
TYPE EVT_BACNET_UNCONF_PRIVATE_XFER : STRUCT
The UnconfirmedPrivateTransfer service hook.
Return: IEC_BACNET_CB_STATUS
- InOut:
Name
Type
Comment
pCBStatus
POINTER TO IEC_BACNET_CB_STATUS
CB-Status returned for the event. CB_STATUS_DEFAULT: The hook did not handle the requests - the BACnet API stack default actions should handle the request. CB_STATUS_OK: The hook completed successfully.
phTransaction
POINTER TO BYTE
This handle identifies the current request in the API’s internal transaction state machine.
sourceAddress
POINTER TO IEC_BACNET_ADDRESS
This is the MAC address of the BACnet addressed device from which the request has been sent.
destinationAddress
POINTER TO IEC_BACNET_ADDRESS
This is the MAC address of the device constructed by the application which has received the request.
pServiceInfo
POINTER TO IEC_BACNET_PRIVATE_TRANSFER_INFO
A pointer to a data structure which contains all service parameters this service provides and the application needs to process.