FBS_ENSWITCH2 (ENUM)ΒΆ
TYPE FBS_ENSWITCH2 :
Definition of SF_EnableSwitch_2 function block states and its diagnostic values.
- Attributes:
qualified_only- InOut:
Name
Initial
Comment
IDLE
16#0
The function block is not active (initial state).
BASIC_OPMODE
16#8002
Safe operation mode is not active.
SAFE_OPMODE
16#8004
Safe operation mode is active.
NOT_ENABLED
16#8802
Safe operation mode is active and the enable switch is in position 1 or 3.
ENABLED
16#8000
Safe operation mode is active and the enable switch is in position 2.
ERR_OPERATION
16#C010
Enable switch not in position 1 during activation of S_SafetyActive. S_EnableIn = TRUE
ERR_OPERATION_RESREQ
16#C410
Enable switch not in position 1 during activation of S_SafetyActive. S_EnableIn = FALSE
ERR_RESET_1
16#C001
Static Reset signal detected in state Cx10.