MaxOnTime (FB)¶
FUNCTION_BLOCK MaxOnTime
“warp clock”-enabled maximum on-time.
If xInput is TRUE MaxOnTime set xOutput to TRUE not longer then tMaxOn. After tMaxOn is expired xOutput is set to FALSE and a new rising edge of xInput is needed to restart the maximum on-time again.
“Warp clock”-enabled¶
Certain application domains base their functionality / algorithms on real world wall clock date/time. To develop such functionality it is helpful to have control over the application timeline to speedup testing or doesnt loose control on the timeline sitting on breakpoints. WarpClock and “warp clock”-enabled function blocks provides such a control if needed. For more details about “warp” time see WarpClock.
To use “warp” time connect an accordingly configured WarpClock to itfDateTimeProvider.
- InOut:
Scope
Name
Type
Initial
Comment
Input
xInputBOOLFALSE
Input
tMaxOnTIMETIME#0ms
Maximum on-time
xResetBOOLFALSE
Reset
itfDateTimeProviderUtil.IDateTimeProviderGlobals.g_dtpDateTimeProvider
Source for the current date and time information in milliseconds since 1.1.1970 00:00:00.000
Output
xOutputBOOLOutput
xErrorBOOLError indication
eErrorIDError ID