EnergyLevelSetpoint (FB)¶
FUNCTION_BLOCK EnergyLevelSetpoint
Selects the energy level releated setpoint of a building (part) or system part (like a HVAC plant powering a building).
The purpose of selecting an energy level is to optimize energy consumption.
EnergyLevelSetpoint differentiates between four levels with increasing energy demands:
“protection”
“economy”
“pre-comfort”
“comfort”
The “protection” energy level is using the minimum energy amount to prevent damage to the building fabric and the building technical installation. The building / system part is controlled using this level if temporarily out of use.
The “economy” energy level is an energy saving mode of a building or system part which is not occupied or not being used for longer periods (at night, weekend etc.). The “pre-comfort” energy level is an energy saving mode of a building or system part which is supposed to reach “comfort” level within a short period. The “comfort” energy level is the state intended for nomal usage of an occupied building.
VDI 3814 reference¶
EnergyLevelSetpoint is oriented towards VDI 3814 3.1 “Optimisation functions” “Energy Mode” (6.3.6.1), but is different in some aspects.
VDI 3814 “Energy Mode” (6.3.6.1) implies some aspects which at least give room for discussions:
room occupation stateandwindow contactOperation mode computation in room controllers is more complex than those two aspects. So EnergyLevelSetpoint doesnt provide those isolated aspects and leaves them up to a more complex room controller function block. Because of this there is no need for an output “current operation mode”.
hysteresis for building protection limitThe “no energy zone” between heat setpoint and cool setpoint is sufficient to ensure building protection and avoiding unneccesary energy consumption. Requesting a hysteresis does imply kind of two-position control - which is neither needed to request nor fully specified in VDI 3814 “Energy Mode”. So EnergyLevelSetpoint doesnt provide this and leaves this aspect up to a more complex room controller function block.
current setpointProviding just one current setpoint does imply single sequence control driven by this setpoint. Control algorithm tend to be more complex than this, multi-sequence-control is quiet often the default. So EnergyLevelSetpoint provides the current heat setpoint and cool setpoint.
- InOut:
Scope
Name
Type
Initial
Comment
Input
eLevelEnergy level
rSetptHeatComfortREAL21.0
Heat setpoint comfort level
rSetptCoolComfortREAL23.0
Cool setpoint comfort level
rSetptHeatPreComfortREAL19.0
Heat setpoint pre-comfort level
rSetptCoolPreComfortREAL25.0
Cool setpoint pre-comfort level
rSetptHeatEconomyREAL16.0
Heat setpoint economy level
rSetptCoolEconomyREAL28.0
Cool setpoint economy level
rSetptHeatProtectionREAL10.0
Heat setpoint protection level
rSetptCoolProtectionREAL40.0
Cool setpoint protection level
Output
rSetptHeatREALCurrent heat setpoint
rSetptCoolREALCurrent cool setpoint