FourToTwoPipes (FB)¶
FUNCTION_BLOCK FourToTwoPipes
Control support for four-to-two-pipe assembly.
Application example¶
A four-to-two-pipe assembly consists of two shut-off valves (for heat / cool pipe) plus a control valve. They are used in plants to connect two-pipe aggregates to four-pipe supply.
Functionality¶
FourToTwoPipes takes care to control the shut-off valves to ensure they are not open in parallel. There are optional service indications (from shut-off valves) and a close-time to achieve this. In the rare case shut-off valves provide service indications it’s advisabe to use them. Otherwise FourToTwoPipes needs to rely on a properly configured close-time definitely covering travel time of shut-off valves plus safety reserve.
By construction four-to-two-pipe assemblies are supposed work in operation modes heat / cool / closed. Setpoints of the heat / cool sequence (0..100%) are scaled to the setting range (r*Begin..r*End - default 0..100%). The valve operation mode eModeIn can eventually provided by a specifc temperatur controller algorithm - in this case eModeOut follows the eModeIn. In case eModeIn is UNUSED, eModeOut is computed comparing rHeatSetpt / rCoolSetpt > 0.
Some controller algorithms may apply control range constraints - eventually a lower limit > 0%. In this case the setpoints of the heat / cool sequences will become inconsistent to determine the valve operation mode from. If the controller algorithm doesnt provides a valve operation mode, but inconsistent heat / cool sequences FourToTwoPipes falls back to heat.
- InOut:
- Scope - Name - Type - Initial - Comment - Input - xEnable- BOOL- TRUE - Enable - rHeat- REAL- Heat control signal (0..100%). - rHeatBegin- REAL- 0.0 - Heat control range begin (0..100%). - rHeatEnd- REAL- 100.0 - Heat control range end (0..100%). - rCool- REAL- Cool control signal (0..100%). - rCoolBegin- REAL- 0.0 - Cool control range begin (0..100%). - rCoolEnd- REAL- 100.0 - Cool control range end (0..100%). - eModeIn- HeatCoolOperationMode.UNUSED - Controller operation mode. - tClose- TIME- TIME#1m0s0ms - Close time - minimum time both shut-off valves needs to be closed. - xSvciHeatClosed- BOOL- FALSE - Service indication - heat shut-off valve is closed - xSvciHeatClosed_Used- BOOL- FALSE - Service indication svciHeatClosed is used / connected. - xSvciCoolClosed- BOOL- FALSE - Service indication - cool shut-off valve is closed - xSvciCoolClosed_Used- BOOL- FALSE - Service indication svciCoolClosed is used / connected. - itfDateTimeProvider- Util.IDateTimeProvider- Globals.g_dtpDateTimeProvider - Source for the current date and time information in milliseconds since 1.1.1970 00:00:00.000 - Output - xHeat- BOOL- Heat shut-off valve - TRUE if open - xCool- BOOL- Cool shut-off valve - TRUE if open - rControl- REAL- Control valve signal (0..100%). - eModeOut- HeatCoolOperationMode.INACTIVE - Operation mode. - xError- BOOL- Error indication - r*End = r*Begin or rSetpt out of range 0..100%. - eErrorID- Error ID 