PumpOnOff (FB)¶
FUNCTION_BLOCK PumpOnOff IMPLEMENTS IActuatorOnOff
Pump on/off.
Application example¶
Pumps are widely used for certain tasks in building automation applications, most prominently:
heating pumps
circulating pumps
Device examples¶
Grundfos ALPHA2 https://product-selection.grundfos.com/de/products/alpha/alpha2?tab=models
Wilo Stratos MAXO https://wilo.com/de/de/Katalog/de/produkte-expertise/wilo-stratos-maxo
Wilo Stratos PICO plus https://wilo.com/de/de/Katalog/de/produkte-expertise/wilo-stratos-pico-plus/stratos-pico-plus-15-1-4
Functionality¶
PumpOnOff controls a pump on/off covering the following aspects:
on / off delay
blocking protection
command execution monitoring using pump service indication
hardware error indication (input)
malfunction detection
malfunction locking
operational time
on / off delay¶
Swichting on / off the pump (xOn) is delayed by given values tOnDelay, tOffDelay. Can be disabled by setting tOnDelay, tOffDelay to T#0S.
blocking protection¶
If pump is not running for a given time tBpMaxOff, run it even if reqest xReqOn = FALSE for a given time tBpTime.
command execution monitoring¶
Functionality of CommandExecutionMonitoring is applied to xSvciOn, xSvciOn_Used, tCemMargin. Can be diabled setting xSvciOn_Used := FALSE and/or tCemMargin := T#0S
malfunction detection¶
If a hardware malfunction is detected via command execution monitoring or hardware error indication (input) xError is set to TRUE, eErrorID is set to Error.HardwareError.
malfunction locking¶
Malfunction locking makes the difference how to handle / recover from a detected hardware malfunction.
Malfunction locking enabled (xMalFuncLock := TRUE): If a malfunction is detected, the pump (xOn) is shut off. If the hardware malfunction is gone, xError / eErrorID and pump shutoff are kept until a reset (xReset := TRUE).
Malfunction locking disabled (xMalFuncLock := FALSE): If a malfunction is detected, the pump (xOn) is NOT shut off. The pump recovers from a hardware malfunction automatically.
- InOut:
Scope
Name
Type
Initial
Comment
Input
xReqOnBOOLFALSE
Control signal - request to switch on pump
tOnDelayTIMETIME#0ms
On-delay
tOffDelayTIMETIME#5m0s0ms
Off-delay
tBpMaxOffTIMETIME#2880m0s0ms
Blocking protection maximum off time
tBpTimeTIMETIME#0ms
Blocking protection time, set to T#0S to disable blocking protection
xSvciOnBOOLFALSE
Service indication - pump is running
xSvciOn_UsedBOOLFALSE
Service indication xSvci is used / connected.
tCemMarginTIMETIME#5s0ms
Command execution monitoring margin time
xErriBOOLFALSE
Error indication - pump is signaling an error
xMalFuncLockBOOLFALSE
Enable the malfunction locking
xOpTimeInitBOOLFALSE
Initialize the operational time with a given value (tInit).
tOpTimeInitLTIMELTIME#0ns
Initialization value
xResetBOOLFALSE
Reset
itfDateTimeProviderUtil.IDateTimeProviderGlobals.g_dtpDateTimeProvider
Source for the current date and time information in milliseconds since 1.1.1970 00:00:00.000
Output
xOnBOOLSwitch on pump
tOpTimeLTIMEOperational time
xErrorBOOLError indication
eErrorIDError ID
itfActuatorOnOffOutput to connect THIS to other function block inputs
Properties:
Structure: