BACnetObjects¶
Function blocks and interfaces used for the device FBs corresponding to BACnet objects. These FBs get created automatically when inserting a BACnet device/object into the device tree.
- Accumulator
- BACnetAccumulator (FunctionBlock)
- AckedTransitions (Property)
- Description (Property)
- DeviceType (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- HighLimit (Property)
- LimitEnable (Property)
- LimitMonitoringInterval (Property)
- LoggingObject (Property)
- LoggingRecord (Property)
- LowLimit (Property)
- MaxPresValue (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- Prescale (Property)
- PresentValue (Property)
- ProfileName (Property)
- PulseRate (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- Scale (Property)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- Units (Property)
- ValueBeforeChange (Property)
- ValueChangeTime (Property)
- ValueSet (Property)
- BACnetAccumulator (FunctionBlock)
- AnalogInput
- BACnetAnalogInput (FunctionBlock)
- AckedTransitions (Property)
- COVIncrement (Property)
- Deadband (Property)
- Description (Property)
- DeviceType (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- HighLimit (Property)
- LimitEnable (Property)
- LowLimit (Property)
- MaxPresValue (Property)
- MinPresValue (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- Resolution (Property)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- Units (Property)
- UpdateInterval (Property)
- BACnetAnalogInput (FunctionBlock)
- AnalogOutput
- BACnetAnalogOutput (FunctionBlock)
- AckedTransitions (Property)
- COVIncrement (Property)
- Deadband (Property)
- Description (Property)
- DeviceType (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- GetPriorityArray (Method)
- HighLimit (Property)
- LimitEnable (Property)
- LowLimit (Property)
- MaxPresValue (Property)
- MinPresValue (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- RelinquishDefault (Property)
- Resolution (Property)
- SetPriorityArray (Method)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- Units (Property)
- WritePresentValueNullWithPriority (Method)
- WritePresentValueWithPriority (Method)
- BACnetAnalogOutput (FunctionBlock)
- AnalogValue
- BACnetAnalogValue (FunctionBlock)
- AckedTransitions (Property)
- COVIncrement (Property)
- Deadband (Property)
- Description (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- GetPriorityArray (Method)
- HighLimit (Property)
- LimitEnable (Property)
- LowLimit (Property)
- MaxPresValue (Property)
- MinPresValue (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- RelinquishDefault (Property)
- Resolution (Property)
- SetPriorityArray (Method)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- Units (Property)
- WritePresentValueNullWithPriority (Method)
- WritePresentValueWithPriority (Method)
- BACnetAnalogValue (FunctionBlock)
- Averaging
- BACnetAveraging (FunctionBlock)
- AttemptedSamples (Property)
- AverageValue (Property)
- Description (Property)
- MaximumValue (Property)
- MaximumValueTimestamp (Property)
- MinimumValue (Property)
- MinimumValueTimestamp (Property)
- ObjectPropertyReference (Property)
- ProfileName (Property)
- ValidSamples (Property)
- VarianceValue (Property)
- WindowInterval (Property)
- WindowSamples (Property)
- BACnetAveraging (FunctionBlock)
- BACnetObjectBase (FunctionBlock)
- DeviceInstNumber (Property)
- GetPropertyAccessRight (Method)
- GetPropertyCallbackAttachment (Method)
- GetPropertyId (Method)
- GetPropertyInstanceStackAllocContentBuffer (Method)
- GetPropertyInstanceWithContentBuffer (Method)
- IsPropertyExistent (Method)
- IsPropertyWriteable (Method)
- NumberOfProperties (Property)
- ObjectID (Property)
- ObjectName (Property)
- SetObjectName (Method)
- SetPropertyAccessRight (Method)
- SetPropertyCallbackAttachment (Method)
- SetPropertyInstance (Method)
- Utilities
- GetBACnetAccumulatorRecordProperty (Method)
- GetBACnetArraySizeOfProperty (Method)
- GetBACnetArraySizeOfTwoProperties (Method)
- GetBACnetBitStringProperty (Method)
- GetBACnetBooleanProperty (Method)
- GetBACnetClientCOVProperty (Method)
- GetBACnetDateProperty (Method)
- GetBACnetDateRangeProperty (Method)
- GetBACnetDateTimeProperty (Method)
- GetBACnetDevObjPropReferenceProperty (Method)
- GetBACnetDoubleProperty (Method)
- GetBACnetEnumeratedProperty (Method)
- GetBACnetObjPropReferenceProperty (Method)
- GetBACnetObjectIDProperty (Method)
- GetBACnetPrescaleProperty (Method)
- GetBACnetRealProperty (Method)
- GetBACnetScaleProperty (Method)
- GetBACnetSetpointReferenceProperty (Method)
- GetBACnetSignedProperty (Method)
- GetBACnetStringProperty (Method)
- GetBACnetTimeProperty (Method)
- GetBACnetTimeStampProperty (Method)
- GetBACnetUnsignedProperty (Method)
- IsBACnetDateTimePropertyUnspecified (Method)
- SetBACnetAccumulatorRecordProperty (Method)
- SetBACnetBitStringProperty (Method)
- SetBACnetBooleanProperty (Method)
- SetBACnetClientCOVProperty (Method)
- SetBACnetDateProperty (Method)
- SetBACnetDateRangeProperty (Method)
- SetBACnetDateTimeProperty (Method)
- SetBACnetDateTimePropertyToUnspecified (Method)
- SetBACnetDevObjPropReferenceProperty (Method)
- SetBACnetDoubleProperty (Method)
- SetBACnetEnumeratedProperty (Method)
- SetBACnetObjPropReferenceProperty (Method)
- SetBACnetObjectIDProperty (Method)
- SetBACnetPrescaleProperty (Method)
- SetBACnetRealProperty (Method)
- SetBACnetScaleProperty (Method)
- SetBACnetSetpointReferenceProperty (Method)
- SetBACnetSignedProperty (Method)
- SetBACnetStringProperty (Method)
- SetBACnetTimeProperty (Method)
- SetBACnetTimeStampProperty (Method)
- SetBACnetUnsignedProperty (Method)
- WritePropertyInstance (Method)
- private
- BinaryInput
- BACnetBinaryInput (FunctionBlock)
- AckedTransitions (Property)
- ActiveText (Property)
- AlarmValue (Property)
- ChangeOfStateCount (Property)
- ChangeOfStateTime (Property)
- Description (Property)
- DeviceType (Property)
- ElapsedActiveTime (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- InactiveText (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- Polarity (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- TimeOfActiveTimeReset (Property)
- TimeOfStateCountReset (Property)
- BACnetBinaryInput (FunctionBlock)
- BinaryOutput
- BACnetBinaryOutput (FunctionBlock)
- AckedTransitions (Property)
- ActiveText (Property)
- ChangeOfStateCount (Property)
- ChangeOfStateTime (Property)
- Description (Property)
- DeviceType (Property)
- ElapsedActiveTime (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- FeedbackValue (Property)
- GetPriorityArray (Method)
- InactiveText (Property)
- MinimumOffTime (Property)
- MinimumOnTime (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- Polarity (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- RelinquishDefault (Property)
- SetPriorityArray (Method)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- TimeOfActiveTimeReset (Property)
- TimeOfStateCountReset (Property)
- WritePresentValueNullWithPriority (Method)
- WritePresentValueWithPriority (Method)
- BACnetBinaryOutput (FunctionBlock)
- BinaryValue
- BACnetBinaryValue (FunctionBlock)
- AckedTransitions (Property)
- ActiveText (Property)
- AlarmValue (Property)
- ChangeOfStateCount (Property)
- ChangeOfStateTime (Property)
- Description (Property)
- ElapsedActiveTime (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- GetPriorityArray (Method)
- InactiveText (Property)
- MinimumOffTime (Property)
- MinimumOnTime (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- RelinquishDefault (Property)
- SetPriorityArray (Method)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- TimeOfActiveTimeReset (Property)
- TimeOfStateCountReset (Property)
- WritePresentValueNullWithPriority (Method)
- WritePresentValueWithPriority (Method)
- BACnetBinaryValue (FunctionBlock)
- Calendar
- Command
- Device
- BACnetDevice (FunctionBlock)
- APDUSegmentTimeout (Property)
- APDUTimeout (Property)
- AlignIntervals (Property)
- ApplicationSoftwareVersion (Property)
- BackupAndRestoreState (Property)
- BackupFailureTimeout (Property)
- BackupPreparationTime (Property)
- DatabaseRevision (Property)
- DaylightSavingsStatus (Property)
- Description (Property)
- FirmwareRevision (Property)
- GetActiveCOVSubscriptions (Method)
- GetActiveVTSessions (Method)
- GetAutoSlaveDiscovery (Method)
- GetConfigurationFiles (Method)
- GetConfigurationFilesCount (Method)
- GetDeviceAddressBinding (Method)
- GetManualSlaveAddressBinding (Method)
- GetRestartNotificationRecipients (Method)
- GetSlaveAddressBinding (Method)
- GetSlaveProxyEnable (Method)
- GetStructuredObjectList (Method)
- GetStructuredObjectListCount (Method)
- GetTimeSynchronizationRecipients (Method)
- GetUTCTimeSynchronizationRecipients (Method)
- GetVTClassesSupported (Method)
- IntervalOffset (Property)
- LastRestartReason (Property)
- LastRestoreTime (Property)
- LocalDate (Property)
- LocalTime (Property)
- Location (Property)
- MaxAPDULengthAccepted (Property)
- MaxInfoFrames (Property)
- MaxMaster (Property)
- MaxSegmentsAccepted (Property)
- ModelName (Property)
- NumberOfAPDURetries (Property)
- ProfileName (Property)
- ProtocolObjectTypesSupported (Property)
- ProtocolRevision (Property)
- ProtocolServicesSupported (Property)
- ProtocolVersion (Property)
- RestoreCompletionTime (Property)
- RestorePreparationTime (Property)
- SegmentationSupported (Property)
- SerialNumber (Property)
- SetActiveCOVSubscriptions (Method)
- SetActiveVTSessions (Method)
- SetAutoSlaveDiscovery (Method)
- SetConfigurationFiles (Method)
- SetDeviceAddressBinding (Method)
- SetManualSlaveAddressBinding (Method)
- SetRestartNotificationRecipients (Method)
- SetSlaveAddressBinding (Method)
- SetSlaveProxyEnable (Method)
- SetStructuredObjectList (Method)
- SetTimeSynchronizationRecipients (Method)
- SetUTCTimeSynchronizationRecipients (Method)
- SetVTClassesSupported (Method)
- SystemStatus (Property)
- TimeOfDeviceRestart (Property)
- TimeSynchronizationInterval (Property)
- UTCOffset (Property)
- VendorIdentifier (Property)
- VendorName (Property)
- BACnetDevice (FunctionBlock)
- EventEnrollment
- BACnetEventEnrollment (FunctionBlock)
- AckedTransitions (Property)
- Description (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- EventType (Property)
- FaultType (Property)
- GetEventParameters (Method)
- GetFaultParameters (Method)
- NotificationClass (Property)
- NotifyType (Property)
- ObjectPropertyReference (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- SetEventParameters (Method)
- SetFaultParameters (Method)
- StatusFlags (Property)
- TimeDelayNormal (Property)
- BACnetEventEnrollment (FunctionBlock)
- EventLog
- BACnetEventLog (FunctionBlock)
- AckedTransitions (Property)
- BufferSize (Property)
- Description (Property)
- Enable (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- LastNotifyRecord (Property)
- LogBuffer
- NotificationClass (Property)
- NotificationThreshold (Property)
- NotifyType (Property)
- ProfileName (Property)
- RecordCount (Property)
- RecordsSinceNotification (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- StartTime (Property)
- StatusFlags (Property)
- StopTime (Property)
- StopWhenFull (Property)
- TotalRecordCount (Property)
- BACnetEventLog (FunctionBlock)
- File
- BACnetFile (FunctionBlock)
- Archive (Property)
- CheckIfFileIsAvailableAtAll (Method)
- Description (Property)
- FileAccessMethod (Property)
- FileSize (Property)
- FileType (Property)
- ModificationDate (Property)
- PLCLocalFileName (Property)
- ProfileName (Property)
- ReadFileModificationTime (Method)
- ReadOnly (Property)
- RecordCount (Property)
- BACnetFile (FunctionBlock)
- Global Group
- BACnetGlobalGroup (FunctionBlock)
- AckedTransitions (Property)
- AddGroupMember (Method)
- COVResubscriptionInterval (Property)
- COVUPeriod (Property)
- ClientCOVIncrement (Property)
- Description (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- GetCOVURecipients (Method)
- GetGroupMember (Method)
- GetGroupMemberCount (Method)
- GetPresentValue (Method)
- MemberStatusFlags (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- RemoveGroupMember (Method)
- RequestedUpdateInterval (Property)
- SetCOVURecipients (Method)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- UpdateInterval (Property)
- BACnetGlobalGroup (FunctionBlock)
- Group
- IBACnetObjectBase (Interface)
- DeviceInstNumber (Property)
- GetPropertyCallbackAttachment (Method)
- GetPropertyId (Method)
- GetPropertyInstance (Method)
- GetPropertyInstanceStackAllocContentBuffer (Method)
- GetPropertyInstanceWithContentBuffer (Method)
- IsPropertyExistent (Method)
- IsPropertyWriteable (Method)
- NumberOfProperties (Property)
- ObjectID (Property)
- ObjectName (Property)
- SetObjectName (Method)
- SetPropertyAccessRight (Method)
- SetPropertyCallbackAttachment (Method)
- SetPropertyInstance (Method)
- Utilities
- GetBACnetAccumulatorRecordProperty (Method)
- GetBACnetBitStringProperty (Method)
- GetBACnetBooleanProperty (Method)
- GetBACnetClientCOVProperty (Method)
- GetBACnetDateProperty (Method)
- GetBACnetDateRangeProperty (Method)
- GetBACnetDateTimeProperty (Method)
- GetBACnetDevObjPropReferenceProperty (Method)
- GetBACnetEnumeratedProperty (Method)
- GetBACnetObjPropReferenceProperty (Method)
- GetBACnetObjectIDProperty (Method)
- GetBACnetPrescaleProperty (Method)
- GetBACnetRealProperty (Method)
- GetBACnetScaleProperty (Method)
- GetBACnetSetpointReferenceProperty (Method)
- GetBACnetSignedProperty (Method)
- GetBACnetStringProperty (Method)
- GetBACnetTimeProperty (Method)
- GetBACnetTimeStampProperty (Method)
- GetBACnetUnsignedProperty (Method)
- SetBACnetAccumulatorRecordProperty (Method)
- SetBACnetBitStringProperty (Method)
- SetBACnetBooleanProperty (Method)
- SetBACnetClientCOVProperty (Method)
- SetBACnetDateProperty (Method)
- SetBACnetDateRangeProperty (Method)
- SetBACnetDateTimeProperty (Method)
- SetBACnetDevObjPropReferenceProperty (Method)
- SetBACnetEnumeratedProperty (Method)
- SetBACnetObjPropReferenceProperty (Method)
- SetBACnetObjectIDProperty (Method)
- SetBACnetPrescaleProperty (Method)
- SetBACnetRealProperty (Method)
- SetBACnetScaleProperty (Method)
- SetBACnetSetpointReferenceProperty (Method)
- SetBACnetSignedProperty (Method)
- SetBACnetStringProperty (Method)
- SetBACnetTimeProperty (Method)
- SetBACnetTimeStampProperty (Method)
- SetBACnetUnsignedProperty (Method)
- WritePropertyInstance (Method)
- IBACnetStaticObjectBase (Interface)
- IntegerValue
- BACnetIntegerValue (FunctionBlock)
- AckedTransitions (Property)
- COVIncrement (Property)
- Deadband (Property)
- Description (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- GetPriorityArray (Method)
- HighLimit (Property)
- LimitEnable (Property)
- LowLimit (Property)
- MaxPresValue (Property)
- MinPresValue (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- RelinquishDefault (Property)
- Resolution (Property)
- SetPriorityArray (Method)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- Units (Property)
- WritePresentValueNullWithPriority (Method)
- WritePresentValueWithPriority (Method)
- BACnetIntegerValue (FunctionBlock)
- LargeAnalogValue
- BACnetLargeAnalogValue (FunctionBlock)
- AckedTransitions (Property)
- COVIncrement (Property)
- Deadband (Property)
- Description (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- GetPriorityArray (Method)
- HighLimit (Property)
- LimitEnable (Property)
- LowLimit (Property)
- MaxPresValue (Property)
- MinPresValue (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- RelinquishDefault (Property)
- Resolution (Property)
- SetPriorityArray (Method)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- Units (Property)
- WritePresentValueNullWithPriority (Method)
- WritePresentValueWithPriority (Method)
- BACnetLargeAnalogValue (FunctionBlock)
- LifeSafetyPoint
- BACnetLifeSafetyPoint (FunctionBlock)
- AckedTransitions (Property)
- Description (Property)
- DeviceType (Property)
- DirectReading (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- GetAcceptedModes (Method)
- GetAlarmValues (Method)
- GetFaultValues (Method)
- GetLifeSafetyAlarmValues (Method)
- GetMemberOf (Method)
- MaintenanceRequired (Property)
- Mode (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OperationExpected (Property)
- OutOfService (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- SetAcceptedModes (Method)
- SetAlarmValues (Method)
- SetFaultValues (Method)
- SetLifeSafetyAlarmValues (Method)
- SetMemberOf (Method)
- Setting (Property)
- Silenced (Property)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- TrackingValue (Property)
- Units (Property)
- BACnetLifeSafetyPoint (FunctionBlock)
- LifeSafetyZone
- BACnetLifeSafetyZone (FunctionBlock)
- AckedTransitions (Property)
- Description (Property)
- DeviceType (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- GetAcceptedModes (Method)
- GetAlarmValues (Method)
- GetFaultValues (Method)
- GetLifeSafetyAlarmValues (Method)
- GetMemberOf (Method)
- GetZoneMembers (Method)
- MaintenanceRequired (Property)
- Mode (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OperationExpected (Property)
- OutOfService (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- SetAcceptedModes (Method)
- SetAlarmValues (Method)
- SetFaultValues (Method)
- SetLifeSafetyAlarmValues (Method)
- SetMemberOf (Method)
- SetZoneMembers (Method)
- Silenced (Property)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- TrackingValue (Property)
- BACnetLifeSafetyZone (FunctionBlock)
- Loop
- BACnetLoop (FunctionBlock)
- AckedTransitions (Property)
- Action_ (Property)
- Bias (Property)
- COVIncrement (Property)
- ControlledVariableReference (Property)
- ControlledVariableUnits (Property)
- ControlledVariableValue (Property)
- Deadband (Property)
- DerivativeConstant (Property)
- DerivativeConstantUnits (Property)
- Description (Property)
- ErrorLimit (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- IntegralConstant (Property)
- IntegralConstantUnits (Property)
- ManipulatedVariableReference (Property)
- MaximumOutput (Property)
- MinimumOutput (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- OutputUnits (Property)
- PresentValue (Property)
- PriorityForWriting (Property)
- ProfileName (Property)
- ProportionalConstant (Property)
- ProportionalConstantUnits (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- Setpoint (Property)
- SetpointReference (Property)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- UpdateInterval (Property)
- BACnetLoop (FunctionBlock)
- MultistateInput
- BACnetMultistateInput (FunctionBlock)
- AckedTransitions (Property)
- Description (Property)
- DeviceType (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- GetAlarmValues (Method)
- GetFaultValues (Method)
- GetStateText (Method)
- NotificationClass (Property)
- NotifyType (Property)
- NumberOfStates (Property)
- OutOfService (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- SetAlarmValues (Method)
- SetFaultValues (Method)
- SetStateText (Method)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- BACnetMultistateInput (FunctionBlock)
- MultistateOutput
- BACnetMultistateOutput (FunctionBlock)
- AckedTransitions (Property)
- Description (Property)
- DeviceType (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- FeedbackValue (Property)
- GetPriorityArray (Method)
- GetStateText (Method)
- NotificationClass (Property)
- NotifyType (Property)
- NumberOfStates (Property)
- OutOfService (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- RelinquishDefault (Property)
- SetPriorityArray (Method)
- SetStateText (Method)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- WritePresentValueNullWithPriority (Method)
- WritePresentValueWithPriority (Method)
- BACnetMultistateOutput (FunctionBlock)
- MultistateValue
- BACnetMultistateValue (FunctionBlock)
- AckedTransitions (Property)
- Description (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- GetAlarmValues (Method)
- GetFaultValues (Method)
- GetPriorityArray (Method)
- GetStateText (Method)
- NotificationClass (Property)
- NotifyType (Property)
- NumberOfStates (Property)
- OutOfService (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- RelinquishDefault (Property)
- SetAlarmValues (Method)
- SetFaultValues (Method)
- SetPriorityArray (Method)
- SetStateText (Method)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- WritePresentValueNullWithPriority (Method)
- WritePresentValueWithPriority (Method)
- BACnetMultistateValue (FunctionBlock)
- NotificationClass
- PositiveIntegerValue
- BACnetPositiveIntegerValue (FunctionBlock)
- AckedTransitions (Property)
- COVIncrement (Property)
- Deadband (Property)
- Description (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- GetPriorityArray (Method)
- HighLimit (Property)
- LimitEnable (Property)
- LowLimit (Property)
- MaxPresValue (Property)
- MinPresValue (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- RelinquishDefault (Property)
- Resolution (Property)
- SetPriorityArray (Method)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- Units (Property)
- WritePresentValueNullWithPriority (Method)
- WritePresentValueWithPriority (Method)
- BACnetPositiveIntegerValue (FunctionBlock)
- Program
- BACnetProgram (FunctionBlock)
- AckedTransitions (Property)
- Description (Property)
- DescriptionOfHalt (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- InstanceOf (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- ProfileName (Property)
- ProgramChange (Property)
- ProgramLocation (Property)
- ProgramState (Property)
- ReasonForHalt (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- StatusFlags (Property)
- BACnetProgram (FunctionBlock)
- PulseConverter
- BACnetPulseConverter (FunctionBlock)
- AckedTransitions (Property)
- AdjustValue (Property)
- COVIncrement (Property)
- COVPeriod (Property)
- Count (Property)
- CountBeforeChange (Property)
- CountChangeTime (Property)
- Deadband (Property)
- Description (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- HighLimit (Property)
- InputReference (Property)
- LimitEnable (Property)
- LowLimit (Property)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- PresentValue (Property)
- ProfileName (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- ScaleFactor (Property)
- StatusFlags (Property)
- TimeDelay (Property)
- TimeDelayNormal (Property)
- Units (Property)
- UpdateTime (Property)
- BACnetPulseConverter (FunctionBlock)
- Schedule
- BACnetSchedule (FunctionBlock)
- AckedTransitions (Property)
- Description (Property)
- EffectivePeriod (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- ExceptionSchedule
- GetPresentValue (Method)
- GetScheduleDefault (Method)
- NotificationClass (Property)
- NotifyType (Property)
- OutOfService (Property)
- PriorityForWriting (Property)
- ProfileName (Property)
- PropertyReferences
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- SetPresentValue (Method)
- SetScheduleDefault (Method)
- StatusFlags (Property)
- WeeklySchedule
- BACnetSchedule (FunctionBlock)
- StructuredView
- TrendLog
- BACnetTrendLog (FunctionBlock)
- AckedTransitions (Property)
- AlignIntervals (Property)
- BufferSize (Property)
- COVResubscriptionInterval (Property)
- ClientCOVIncrement (Property)
- Description (Property)
- Enable (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- IntervalOffset (Property)
- LastNotifyRecord (Property)
- LogBuffer
- LogDeviceObjectProperty (Property)
- LogInterval (Property)
- LoggingType (Property)
- NotificationClass (Property)
- NotificationThreshold (Property)
- NotifyType (Property)
- ProfileName (Property)
- RecordCount (Property)
- RecordsSinceNotification (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- StartTime (Property)
- StatusFlags (Property)
- StopTime (Property)
- StopWhenFull (Property)
- TotalRecordCount (Property)
- Trigger (Property)
- BACnetTrendLog (FunctionBlock)
- TrendLogMultiple
- BACnetTrendLogMultiple (FunctionBlock)
- AckedTransitions (Property)
- AddLogPropertyReference (Method)
- AlignIntervals (Property)
- BufferSize (Property)
- Description (Property)
- Enable (Property)
- EventAlgorithmInhibit (Property)
- EventAlgorithmInhibitRef (Property)
- EventDetectionEnable (Property)
- EventEnable (Property)
- EventMessageTexts (Property)
- EventMessageTextsConfig (Property)
- EventState (Property)
- EventTimeStamps (Property)
- GetLogPropertyReference (Method)
- GetLogPropertyReferenceCount (Method)
- IntervalOffset (Property)
- LastNotifyRecord (Property)
- LogBuffer
- LogInterval (Property)
- LoggingType (Property)
- NotificationClass (Property)
- NotificationThreshold (Property)
- NotifyType (Property)
- ProfileName (Property)
- RecordCount (Property)
- RecordsSinceNotification (Property)
- Reliability (Property)
- ReliabilityEvaluationInhibit (Property)
- RemoveLogPropertyReference (Method)
- StartTime (Property)
- StatusFlags (Property)
- StopTime (Property)
- StopWhenFull (Property)
- TotalRecordCount (Property)
- Trigger (Property)
- BACnetTrendLogMultiple (FunctionBlock)