BACnetClientRemoveListElement (FB)¶
FUNCTION_BLOCK PUBLIC FINAL BACnetClientRemoveListElement EXTENDS BACnetClientBase
Common Behaviour Model conform (ETrigA) FB to execute a Remove-List-Element-Request in the BACnet-Network. If execution completed successfully and xDone is TRUE, the Remove-List-Element-Request was successful. In any other case eStatus and errorResult may hold additional information of what failed and firstFailed holds the index of the first element, which failed to be removed.
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
xExecuteBOOLRising edge: Starts defined operationFALSE: Resets the defined operation after ready condition was reachedETrigATo
xAbortBOOLTRUE: Aborts the operationETrigATo
udiTimeOutUDINTMax. operating time for executing [µs], 0: No operating time limit
ETrigATo
Output
xDoneBOOLTRUE: Ready condition reachedETrigATo
xBusyBOOLTRUE: Operation is runningETrigATo
xErrorBOOLTRUE: Error condition reachedETrigATo
xAbortedBOOLTRUE: Abort condition reachedETrigATo
Input
dwTargetDeviceNumberDWORDThe device number of the targeted device in the BACnet- Network.
pTargetDeviceAddressPOINTER TO CmpBACnet.IEC_BACNET_ADDRESS
0
Optional: The device address of the targeted device in the BACnet-Network. If an adress is given the given device number is ignored.
Output
eStatusCmpBACnet.IEC_BACNET_STATUSCmpBACnet.IEC_BACNET_STATUS.BACNET_STATUS_OK
If an error occured, the error state.
errorResultCmpBACnet.IEC_BACNET_ERRORSTRUCT(tag := CmpBACnet.IEC_BACNET_FAILURE_TYPE._FAILURE_MAX_SIZE)
If an error occured (this means eStatus <> BACNET_STATUS_OK), whereas the sent BACnet-Request was answered with an specific error information, the latter is contained in this structure.
iStateDINT0
- The State in which the FB is during execution:
0: No execution, resetted state
1: Searching for the Target-Device and a valid address for it
2: Sending the BACnet-Request into the network
3: Waiting for the answer (if there is one) to the BACnet-Request made in 2
4: Finishing the call, setting of the output variables
Input
objTypeCmpBACnet.IEC_BACNET_OBJECT_TYPEThe type of the object under the targeted device to remove a list element from.
objInstCmpBACnet.IEC_BACNET_DWORDThe instance number of the object under the targeted device to remove a list element from.
propIDCmpBACnet.IEC_BACNET_PROPERTY_IDThe property ID of the property of the object under the targeted device to remove a list element from.
nIndexCmpBACnet.IEC_BACNET_SIGNEDThe Index of the element in the property, where the elements of property Contents shall be removed.
elementsCmpBACnet.IEC_BACNET_PROPERTY_CONTENTSThe elements to be removed from the property (compare elements.nElements).
Output
firstFailedCmpBACnet.IEC_BACNET_UNSIGNEDIf the Remove-List-Element-Request failed, this variable holds the index of the first element, which failed to be removed.
Properties:
Instance, inherited from BACnetClientBase
Running, inherited from BACnetClientBase
Server, inherited from BACnetClientBase
SourceDeviceAddress, inherited from BACnetClientBase
SourceDeviceNumber, inherited from BACnetClientBase
TargetDeviceAddress, inherited from BACnetClientBase
TargetDeviceNumber, inherited from BACnetClientBase
Methods:
RegisterToServer, inherited from BACnetClientBase
UnregisterFromServer, inherited from BACnetClientBase
Structure: