BACnetClientConfPrivateTransfer (FB)¶
FUNCTION_BLOCK PUBLIC FINAL BACnetClientConfPrivateTransfer EXTENDS BACnetClientBase
Common Behaviour Model conform (ETrigA) FB to execute a ConfirmedPrivateTransfer-Request in the BACnet-Network. If execution completed successfully and xDone is TRUE, result is filled with valid data, in any other case the data in result are not valid.
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
xExecute
BOOL
Rising edge: Starts defined operationFALSE
: Resets the defined operation after ready condition was reachedETrigATo
xAbort
BOOL
TRUE
: Aborts the operationETrigATo
udiTimeOut
UDINT
Max. operating time for executing [µs], 0: No operating time limit
ETrigATo
Output
xDone
BOOL
TRUE
: Ready condition reachedETrigATo
xBusy
BOOL
TRUE
: Operation is runningETrigATo
xError
BOOL
TRUE
: Error condition reachedETrigATo
xAborted
BOOL
TRUE
: Abort condition reachedETrigATo
Input
dwTargetDeviceNumber
DWORD
The device number of the targeted device in the BACnet- Network.
pTargetDeviceAddress
POINTER TO CmpBACnet.IEC_BACNET_ADDRESS
0
Optional: The device address of the targeted device in the BACnet-Network. If an adress is given the given device number is ignored.
Output
eStatus
CmpBACnet.IEC_BACNET_STATUS
CmpBACnet.IEC_BACNET_STATUS.BACNET_STATUS_OK
If an error occured, the error state.
errorResult
CmpBACnet.IEC_BACNET_ERROR
STRUCT(tag := CmpBACnet.IEC_BACNET_FAILURE_TYPE._FAILURE_MAX_SIZE)
If an error occured (this means eStatus <> BACNET_STATUS_OK), whereas the sent BACnet-Request was answered with an specific error information, the latter is contained in this structure.
iState
DINT
0
- The State in which the FB is during execution:
0: No execution, resetted state
1: Searching for the Target-Device and a valid address for it
2: Sending the BACnet-Request into the network
3: Waiting for the answer (if there is one) to the BACnet-Request made in 2
4: Finishing the call, setting of the output variables
Input
nVendorID
CmpBACnet.IEC_BACNET_UNSIGNED
This parameter, of type Unsigned, specifies the unique vendor identification code for the type of vendor-proprietary service to be performed.
nServiceNumber
CmpBACnet.IEC_BACNET_UNSIGNED
This parameter, of type Unsigned, specifies the desired service to be performed.
fParametersPresent
CmpBACnet.IEC_BACNET_BOOLEAN
If set to True the parameters value is valid.
parameters
CmpBACnet.IEC_BACNET_BUFFER
This optional parameter shall transport additional parameters for the service specified by ‘Vendor ID’ and ‘Service Number’. The datatype and interpretation of these parameters is a local matter.
nByteCount
CmpBACnet.IEC_BACNET_UNSIGNED
This is the size of the filled bytes in the parameters buffer on reply to the confirmed service variant of this type.
Output
result
CmpBACnet.IEC_BACNET_PRIVATE_TRANSFER_INFO
If the BACnet-Request succeeded (xDone is TRUE and no error occured (xError is FALSE)), this variable holds the result of the request.
Properties:
Instance, inherited from BACnetClientBase
Running, inherited from BACnetClientBase
Server, inherited from BACnetClientBase
SourceDeviceAddress, inherited from BACnetClientBase
SourceDeviceNumber, inherited from BACnetClientBase
TargetDeviceAddress, inherited from BACnetClientBase
TargetDeviceNumber, inherited from BACnetClientBase
Methods:
RegisterToServer, inherited from BACnetClientBase
UnregisterFromServer, inherited from BACnetClientBase
Structure: