BACnetClientWriteProperty (FB)¶
FUNCTION_BLOCK PUBLIC FINAL BACnetClientWriteProperty EXTENDS BACnetClientBase
Common Behaviour Model conform (ETrigA) FB to execute a Write-Property-Request in the BACnet-Network. If execution completed successfully and xDone is TRUE, the Write-Request was successful. In any other case eStatus and errorResult may hold additional information of what failed.
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
xExecuteBOOLRising edge: Starts defined operationFALSE: Resets the defined operation after ready condition was reachedETrigATo
xAbortBOOLTRUE: Aborts the operationETrigATo
udiTimeOutUDINTMax. operating time for executing [µs], 0: No operating time limit
ETrigATo
Output
xDoneBOOLTRUE: Ready condition reachedETrigATo
xBusyBOOLTRUE: Operation is runningETrigATo
xErrorBOOLTRUE: Error condition reachedETrigATo
xAbortedBOOLTRUE: Abort condition reachedETrigATo
Input
dwTargetDeviceNumberDWORDThe device number of the targeted device in the BACnet- Network.
pTargetDeviceAddressPOINTER TO CmpBACnet.IEC_BACNET_ADDRESS
0
Optional: The device address of the targeted device in the BACnet-Network. If an adress is given the given device number is ignored.
Output
eStatusCmpBACnet.IEC_BACNET_STATUSCmpBACnet.IEC_BACNET_STATUS.BACNET_STATUS_OK
If an error occured, the error state.
errorResultCmpBACnet.IEC_BACNET_ERRORSTRUCT(tag := CmpBACnet.IEC_BACNET_FAILURE_TYPE._FAILURE_MAX_SIZE)
If an error occured (this means eStatus <> BACNET_STATUS_OK), whereas the sent BACnet-Request was answered with an specific error information, the latter is contained in this structure.
iStateDINT0
- The State in which the FB is during execution:
0: No execution, resetted state
1: Searching for the Target-Device and a valid address for it
2: Sending the BACnet-Request into the network
3: Waiting for the answer (if there is one) to the BACnet-Request made in 2
4: Finishing the call, setting of the output variables
Input
objTypeCmpBACnet.IEC_BACNET_OBJECT_TYPEThe type of the object under the targeted device to write the property to.
objInstCmpBACnet.IEC_BACNET_DWORDThe instance number of the object under the targeted device to write the property to.
propIDCmpBACnet.IEC_BACNET_PROPERTY_IDThe property ID of the property of the object under the targeted device to write.
nWritePriorityCmpBACnet.IEC_BACNET_SIGNEDThe priority used to write the property. Must be a value within 1..16.
propertyContentsCmpBACnet.IEC_BACNET_PROPERTY_CONTENTSThe contents to be written into the property.
nIndexCmpBACnet.IEC_BACNET_SIGNED-1
Optional: The Index of the element of the property written. Only use for constant array properties. Otherwise use index -1 or leave empty.
Properties:
Instance, inherited from BACnetClientBase
Running, inherited from BACnetClientBase
Server, inherited from BACnetClientBase
SourceDeviceAddress, inherited from BACnetClientBase
SourceDeviceNumber, inherited from BACnetClientBase
TargetDeviceAddress, inherited from BACnetClientBase
TargetDeviceNumber, inherited from BACnetClientBase
Methods:
InitializeOutputs, inherited from BACnetClientBase
RegisterToServer, inherited from BACnetClientBase
UnregisterFromServer, inherited from BACnetClientBase
Structure: