SF_EDM (FB)¶
FUNCTION_BLOCK SF_EDM
- InOut:
Scope
Name
Type
Initial
Comment
Input
ActivateBOOLFALSE
Activation of the FB.
S_OutControlBOOLFALSE
Control signal of the preceeding safety FBs.
EDM1BOOLFALSE
Feedback signal of the first connected actuator.
EDM2BOOLFALSE
Feedback signal of the second connected actuator.
MonitoringTimeTIMETIME#0ms
Maximum response time of the connected and monitored actuators.
ResetBOOLFALSE
Manual reset of FB
Output
ReadyBOOLFALSE
Activation of the FB. TRUE indicates that the FB is activated and the outputs results are valid, FALSE the FB is not active and the program is not executed.
S_EDM_OutBOOLFALSE
Controls the actuator. The result is monitored by the feed- back signal EDMx.
SafetyDemandBOOLFALSE
Output indicating that the FB is active and the primary safety function is demanded (e.g. related to the safety functionality).
ResetRequestBOOLFALSE
Output which can be used to signal the operator to press the reset functionality to continue.
ErrorBOOLFALSE
Error flag
DiagCodeWORD0
Diagnostic register