FBS_ENSWITCH2 (ENUM)ΒΆ

TYPE FBS_ENSWITCH2 :

Definition of SF_EnableSwitch_2 function block states and its diagnostic values.

Attributes:
qualified_only
InOut:

Name

Initial

Comment

IDLE

16#0

The function block is not active (initial state).

BASIC_OPMODE

16#8002

Safe operation mode is not active.

SAFE_OPMODE

16#8004

Safe operation mode is active.

NOT_ENABLED

16#8802

Safe operation mode is active and the enable switch is in position 1 or 3.

ENABLED

16#8000

Safe operation mode is active and the enable switch is in position 2.

ERR_OPERATION

16#C010

Enable switch not in position 1 during activation of S_SafetyActive. S_EnableIn = TRUE

ERR_OPERATION_RESREQ

16#C410

Enable switch not in position 1 during activation of S_SafetyActive. S_EnableIn = FALSE

ERR_RESET_1

16#C001

Static Reset signal detected in state Cx10.