ETC_CO_SdoRead_Channel (FB)ΒΆ
FUNCTION_BLOCK ETC_CO_SdoRead_Channel
Like ETC_CO_SdoRead_Access, this function block is for reading all EtherCAT slave parameters.
There is an additional input, byChannelPriority (BYTE), with which the channel and priority can be specified in the CoE mailbox message. The first 6 bits specify the channel, the final 2 bits the priority.
- InOut:
- Scope - Name - Type - Initial - Comment - Input - xExecute- BOOL- Rising edge: ACTION starts Falling edge: Resets outputs If a falling edge occurs before the function block has completed its action, the outputs operate in the usual manner and are only reset if either the action is completed or in the event of an error. In this case, the corresponding output values (xDone, xError) are present at the outputs for exactly one cycle. - xAbort- BOOL- FALSE - TRUE: Action is stopped immediately and all outputs are reset to their initial values. - usiCom- USINT- 1 - Index of master 1: first ETC master - uiDevice- UINT- The physical slave address to access the EtherCAT slave - usiChannel- USINT- 1 - not used in the moment because channel is set automatically - wIndex- WORD- The index of the CoE object - bySubindex- BYTE- The sub index of the CoE object - udiTimeOut- UDINT- Timeout for operation in ms - pBuffer- CAA.PVOID- 0 - Pointer to the buffer for reading the data - szSize- CAA.SIZE- 0 - Size of buffer to store the data - xCompleteAccess- BOOL- FALSE - Object should be read with complete access (all subobjects) - byChannelPriority- BYTE- 0 - The special channel priority in the mailbox message could be set with this input - Output - xDone- BOOL- TRUE: Action successfully completed - xBusy- BOOL- TRUE: Function block active - xError- BOOL- TRUE: Error occurred, function block aborts action, FALSE: No error - eError- If xError is true then eError shows the error reason - udiSdoAbort- UDINT- The abort code as received from the slave device - szDataRead- CAA.SIZE- Number of bytes successfully read