ETC_CO_SdoRead (FB)ΒΆ
FUNCTION_BLOCK ETC_CO_SdoRead
This function block serves to read EtherCAT slave parameters. Unlike ETC_CO_SdoRead4, parameter longer than 4 bytes are also supported. The parameters to be read are specified with Index and Subindex, as used in the object directory.
- InOut:
- Scope - Name - Type - Initial - Comment - Input - xExecute- BOOL- Rising edge: ACTION starts Falling edge: Resets outputs If a falling edge occurs before the function block has completed its action, the outputs operate in the usual manner and are only reset if either the action is completed or in the event of an error. In this case, the corresponding output values (xDone, xError) are present at the outputs for exactly one cycle. - xAbort- BOOL- FALSE - TRUE: Action is stopped immediately and all outputs are reset to their initial values. - usiCom- USINT- 1 - Index of master 1: first ETC master - uiDevice- UINT- The physical slave address to access the EtherCAT slave - usiChannel- USINT- 1 - not used in the moment because channel is set automatically - wIndex- WORD- The index of the CoE object - bySubindex- BYTE- The sub index of the CoE object - udiTimeOut- UDINT- Timeout for operation in ms - pBuffer- CAA.PVOID- 0 - Pointer to the buffer for reading the data - szSize- CAA.SIZE- 0 - Size of buffer to store the data - Output - xDone- BOOL- TRUE: Action successfully completed - xBusy- BOOL- TRUE: Function block active - xError- BOOL- TRUE: Error occurred, function block aborts action, FALSE: No error - eError- If xError is true then eError shows the error reason - udiSdoAbort- UDINT- The abort code as received from the slave device - szDataRead- CAA.SIZE- Number of bytes successfully read