BACnetClientRemoveListElement (FB)¶
FUNCTION_BLOCK PUBLIC FINAL BACnetClientRemoveListElement EXTENDS BACnetClientBase
Common Behaviour Model conform (ETrigA) FB to execute a Remove-List-Element-Request in the BACnet-Network. If execution completed successfully and xDone is TRUE, the Remove-List-Element-Request was successful. In any other case eStatus and errorResult may hold additional information of what failed and firstFailed holds the index of the first element, which failed to be removed.
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
xExecute
BOOL
Rising edge: Starts defined operationFALSE
: Resets the defined operation after ready condition was reachedETrigATo
xAbort
BOOL
TRUE
: Aborts the operationETrigATo
udiTimeOut
UDINT
Max. operating time for executing [µs], 0: No operating time limit
ETrigATo
Output
xDone
BOOL
TRUE
: Ready condition reachedETrigATo
xBusy
BOOL
TRUE
: Operation is runningETrigATo
xError
BOOL
TRUE
: Error condition reachedETrigATo
xAborted
BOOL
TRUE
: Abort condition reachedETrigATo
Input
dwTargetDeviceNumber
DWORD
The device number of the targeted device in the BACnet- Network.
pTargetDeviceAddress
POINTER TO CmpBACnet.IEC_BACNET_ADDRESS
0
Optional: The device address of the targeted device in the BACnet-Network. If an adress is given the given device number is ignored.
pAPDUParams
POINTER TO CmpBACnet.IEC_BACNET_APDU_PROPERTIES
0
A pointer to the structure which contains a set of APDU properties to control the timing and size of transmitted frames for this request. It temporarily overwrites the global APDU settings made in the source device from which this request is sent and which parameters would control this request if this pointer is NULL.
Output
eStatus
CmpBACnet.IEC_BACNET_STATUS
CmpBACnet.IEC_BACNET_STATUS.BACNET_STATUS_OK
If an error occured, the error state.
errorResult
CmpBACnet.IEC_BACNET_ERROR
STRUCT(tag := CmpBACnet.IEC_BACNET_FAILURE_TYPE._FAILURE_MAX_SIZE)
If an error occured (this means eStatus <> BACNET_STATUS_OK), whereas the sent BACnet-Request was answered with an specific error information, the latter is contained in this structure.
iState
DINT
0
- The State in which the FB is during execution:
0: No execution, resetted state
1: Searching for the Target-Device and a valid address for it
2: Sending the BACnet-Request into the network
3: Waiting for the answer (if there is one) to the BACnet-Request made in 2
4: Finishing the call, setting of the output variables
Input
objType
CmpBACnet.IEC_BACNET_OBJECT_TYPE
The type of the object under the targeted device to remove a list element from.
objInst
CmpBACnet.IEC_BACNET_DWORD
The instance number of the object under the targeted device to remove a list element from.
propID
CmpBACnet.IEC_BACNET_PROPERTY_ID
The property ID of the property of the object under the targeted device to remove a list element from.
nIndex
CmpBACnet.IEC_BACNET_ARRAY_INDEX
The Index of the element in the property, where the elements of property Contents shall be removed.
elements
CmpBACnet.IEC_BACNET_PROPERTY_CONTENTS
The elements to be removed from the property (compare elements.nElements).
pValueSrc
POINTER TO CmpBACnet.IEC_BACNET_AUDIT_VALUE_SOURCE
0
Optional: A pointer to a data structure which contains the value source information for generating an logged and/or reported audit notification for this initiated request. If generating an logged and/or reported audit notification for this request is not intended, pValueSrc can be set to 0.
Output
firstFailed
CmpBACnet.IEC_BACNET_UNSIGNED
If the Remove-List-Element-Request failed, this variable holds the index of the first element, which failed to be removed.
Properties:
Instance, inherited from BACnetClientBase
Running, inherited from BACnetClientBase
Server, inherited from BACnetClientBase
SourceDeviceAddress, inherited from BACnetClientBase
SourceDeviceNumber, inherited from BACnetClientBase
TargetDeviceAddress, inherited from BACnetClientBase
TargetDeviceNumber, inherited from BACnetClientBase
Methods:
RegisterToServer, inherited from BACnetClientBase
UnregisterFromServer, inherited from BACnetClientBase
Structure: