BACnetClientGetEventInfo (FB)¶
FUNCTION_BLOCK PUBLIC FINAL BACnetClientGetEventInfo EXTENDS BACnetClientBase
Common Behaviour Model conform (ETrigA) FB to execute a Get-Enrollment-Summary-Reqeust in the BACnet-Network. If execution completed successfully, xDone is set to TRUE.
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
xExecuteBOOLRising edge: Starts defined operationFALSE: Resets the defined operation after ready condition was reachedETrigATo
xAbortBOOLTRUE: Aborts the operationETrigATo
udiTimeOutUDINTMax. operating time for executing [µs], 0: No operating time limit
ETrigATo
Output
xDoneBOOLTRUE: Ready condition reachedETrigATo
xBusyBOOLTRUE: Operation is runningETrigATo
xErrorBOOLTRUE: Error condition reachedETrigATo
xAbortedBOOLTRUE: Abort condition reachedETrigATo
Input
dwTargetDeviceNumberDWORDThe device number of the targeted device in the BACnet- Network.
pTargetDeviceAddressPOINTER TO CmpBACnet.IEC_BACNET_ADDRESS
0
Optional: The device address of the targeted device in the BACnet-Network. If an adress is given the given device number is ignored.
pAPDUParamsPOINTER TO CmpBACnet.IEC_BACNET_APDU_PROPERTIES
0
A pointer to the structure which contains a set of APDU properties to control the timing and size of transmitted frames for this request. It temporarily overwrites the global APDU settings made in the source device from which this request is sent and which parameters would control this request if this pointer is NULL.
Output
eStatusCmpBACnet.IEC_BACNET_STATUSCmpBACnet.IEC_BACNET_STATUS.BACNET_STATUS_OK
If an error occured, the error state.
errorResultCmpBACnet.IEC_BACNET_ERRORSTRUCT(tag := CmpBACnet.IEC_BACNET_FAILURE_TYPE._FAILURE_MAX_SIZE)
If an error occured (this means eStatus <> BACNET_STATUS_OK), whereas the sent BACnet-Request was answered with an specific error information, the latter is contained in this structure.
iStateDINT0
- The State in which the FB is during execution:
0: No execution, resetted state
1: Searching for the Target-Device and a valid address for it
2: Sending the BACnet-Request into the network
3: Waiting for the answer (if there is one) to the BACnet-Request made in 2
4: Finishing the call, setting of the output variables
Input
xLastReceivedPresentBOOLDetermines whether the following lastReceivedType and lastReceivedInst parameters shall be used.
lastReceivedTypeCmpBACnet.IEC_BACNET_OBJECT_TYPEType of the last object type received by the GetEventInfo call.
lastReceivedInstCmpBACnet.IEC_BACNET_DWORDType of the last object instance received by the GetEventInfo call.
Output
resultCmpBACnet.IEC_BACNET_EVENT_INFOIf the BACnet-Request succeeded (xDone is TRUE and no error occured (xError is FALSE)), this variable holds the contents of the event info.
Properties:
Instance, inherited from BACnetClientBase
Running, inherited from BACnetClientBase
Server, inherited from BACnetClientBase
SourceDeviceAddress, inherited from BACnetClientBase
SourceDeviceNumber, inherited from BACnetClientBase
TargetDeviceAddress, inherited from BACnetClientBase
TargetDeviceNumber, inherited from BACnetClientBase
Methods:
RegisterToServer, inherited from BACnetClientBase
UnregisterFromServer, inherited from BACnetClientBase
Structure: