BACnetClientConfPrivateTransfer (FB)¶
FUNCTION_BLOCK PUBLIC FINAL BACnetClientConfPrivateTransfer EXTENDS BACnetClientBase
Common Behaviour Model conform (ETrigA) FB to execute a ConfirmedPrivateTransfer-Request in the BACnet-Network. If execution completed successfully and xDone is TRUE, result is filled with valid data, in any other case the data in result are not valid.
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
xExecuteBOOLRising edge: Starts defined operationFALSE: Resets the defined operation after ready condition was reachedETrigATo
xAbortBOOLTRUE: Aborts the operationETrigATo
udiTimeOutUDINTMax. operating time for executing [µs], 0: No operating time limit
ETrigATo
Output
xDoneBOOLTRUE: Ready condition reachedETrigATo
xBusyBOOLTRUE: Operation is runningETrigATo
xErrorBOOLTRUE: Error condition reachedETrigATo
xAbortedBOOLTRUE: Abort condition reachedETrigATo
Input
dwTargetDeviceNumberDWORDThe device number of the targeted device in the BACnet- Network.
pTargetDeviceAddressPOINTER TO CmpBACnet.IEC_BACNET_ADDRESS
0
Optional: The device address of the targeted device in the BACnet-Network. If an adress is given the given device number is ignored.
pAPDUParamsPOINTER TO CmpBACnet.IEC_BACNET_APDU_PROPERTIES
0
A pointer to the structure which contains a set of APDU properties to control the timing and size of transmitted frames for this request. It temporarily overwrites the global APDU settings made in the source device from which this request is sent and which parameters would control this request if this pointer is NULL.
Output
eStatusCmpBACnet.IEC_BACNET_STATUSCmpBACnet.IEC_BACNET_STATUS.BACNET_STATUS_OK
If an error occured, the error state.
errorResultCmpBACnet.IEC_BACNET_ERRORSTRUCT(tag := CmpBACnet.IEC_BACNET_FAILURE_TYPE._FAILURE_MAX_SIZE)
If an error occured (this means eStatus <> BACNET_STATUS_OK), whereas the sent BACnet-Request was answered with an specific error information, the latter is contained in this structure.
iStateDINT0
- The State in which the FB is during execution:
0: No execution, resetted state
1: Searching for the Target-Device and a valid address for it
2: Sending the BACnet-Request into the network
3: Waiting for the answer (if there is one) to the BACnet-Request made in 2
4: Finishing the call, setting of the output variables
Input
nVendorIDCmpBACnet.IEC_BACNET_UNSIGNEDThis parameter, of type Unsigned, specifies the unique vendor identification code for the type of vendor-proprietary service to be performed.
nServiceNumberCmpBACnet.IEC_BACNET_UNSIGNEDThis parameter, of type Unsigned, specifies the desired service to be performed.
fParametersPresentCmpBACnet.IEC_BACNET_BOOLEANIf set to True the parameters value is valid.
parametersCmpBACnet.IEC_BACNET_BUFFERThis optional parameter shall transport additional parameters for the service specified by ‘Vendor ID’ and ‘Service Number’. The datatype and interpretation of these parameters is a local matter.
nByteCountCmpBACnet.IEC_BACNET_UNSIGNEDThis is the size of the filled bytes in the parameters buffer on reply to the confirmed service variant of this type.
Output
resultCmpBACnet.IEC_BACNET_PRIVATE_TRANSFER_INFOIf the BACnet-Request succeeded (xDone is TRUE and no error occured (xError is FALSE)), this variable holds the result of the request.
Properties:
Instance, inherited from BACnetClientBase
Running, inherited from BACnetClientBase
Server, inherited from BACnetClientBase
SourceDeviceAddress, inherited from BACnetClientBase
SourceDeviceNumber, inherited from BACnetClientBase
TargetDeviceAddress, inherited from BACnetClientBase
TargetDeviceNumber, inherited from BACnetClientBase
Methods:
RegisterToServer, inherited from BACnetClientBase
UnregisterFromServer, inherited from BACnetClientBase
Structure: