IObjectDictionary.WriteObjectByAddress (METH)ΒΆ
METHOD WriteObjectByAddress : ABORT_CODE
Used to write an object in the local object dictionary. If ABORT_CODE.SUCCESSFUL is returned data in pbyData was copied to the object.
If error occured the corresponding abort code is returned.
- InOut:
- Scope - Name - Type - Initial - Comment - Return - WriteObjectByAddress- ABORT_CODE.SUCCESSFUL: Writing successful, object value was changed according to pbyData; ELSE: Writing not permitted. - Input - wIndex- WORD- Index of object which should be written - bySubIndex- BYTE- Subindex of object - xCheckAccess- BOOL- TRUE - TRUE: Access rights should be checked. Write on readonly object will fail. FALSE: Ignore access rights and force writing. - xDataInBusOrder- BOOL- Specifies Byte Order of data - pbyDatapoints to; TRUE: Data in CANopen Byteorder (Little Endian), FALSE: Data in Host Byte Order- pbyData- POINTER TO BYTE - Pointer to data which should be written to the object - Inout - udiSize- UDINT- VAR IN: Size of memory pbyData points to; VAR OUT: Size of Object 
