ScriptDeviceObject¶
- class ScriptDeviceObject.DeviceTrackingMode(value, names=None, *, module=None, qualname=None, type=None, start=1, boundary=None)¶
Bases:
EnumEnumeration that defines how a device is tracked on the network.
- Name = 0¶
Tracked by name (e.g. ‘MyPlc’).
- SystemAddress = 1¶
Tracked by system address (e.g. ‘[056D]’).
- IPAddressUdp = 2¶
Tracked by IP using UDP broadcasts.
- IPAddressTcp = 3¶
Tracked by IP using TCP point-to-point connection.
- Gateway = 4¶
Device is a Gateway and will not be tracked.
- Dummy = 5¶
Placeholder device will not be tracked.
- DNS = 6¶
Tracked by Dns-Address using TCP point-to-point connection.
- class ScriptDeviceObject.StopResetBehaviour(value, names=None, *, module=None, qualname=None, type=None, start=1, boundary=None)¶
Bases:
Enum- KeepCurrentValues = 0¶
The outputs keep the last current values.
- SetToDefault = 1¶
The outputs are set to the default values.
- ExecuteProgram = 2¶
A user defined program is executed.
- class ScriptDeviceObject.ConnectorRole(value, names=None, *, module=None, qualname=None, type=None, start=1, boundary=None)¶
Bases:
EnumDescribes the role of a connector
- Parent = 0¶
The connector allows other devices to be connected to the connectors device.
- Child = 1¶
The connector allows its device to be connected to another device.
- class ScriptDeviceObject.AccessRight(value, names=None, *, module=None, qualname=None, type=None, start=1, boundary=None)¶
Bases:
EnumDefines access rights on a parameter.
- None = (0,)¶
The element is not accessible.
- Read = 1¶
Specifies that the element may be read.
- Write = 2¶
Specifies that it is allowed to write to the element.
- ReadWrite = 3¶
Combination of read and write access: The element may be written and read.
- class ScriptDeviceObject.ChannelType(value, names=None, *, module=None, qualname=None, type=None, start=1, boundary=None)¶
Bases:
EnumDefines the types of a channel.
- None = 0¶
Not a channel.
- Input = 1¶
An input channel.
- Output = 2¶
An output channel.
- OutputReadOnly = 3¶
A readonly output channel.
- class ScriptDeviceObject.DiagType(value, names=None, *, module=None, qualname=None, type=None, start=1, boundary=None)¶
Bases:
EnumDescribes the function of a parameter in respect to module diagnosis.
- None = (0,)¶
No diagnostic meaning
- Diagnosis = (1,)¶
Provides the diagnostic message
- Acknowledge = 2¶
Acknowledge for current diagnostic message
- class ScriptDeviceObject.ScriptDeviceObjectMarker¶
Bases:
objectEvery ScriptObject instance will be extended with this method.
- property is_device¶
Gets a value indicating whether this instance is a device object.
- Return type:
bool
- class ScriptDeviceObject.ScriptDeviceObject¶
Bases:
ScriptDeviceObjectMarkerFunctionality for manipulating device objects.
All device objects implementing DeviceObject will be extended with this methods.
- enable()¶
Marks this device as enabled during download.
- disable()¶
Marks this device as disabled during download.
- is_enabled()¶
Determines whether this instance is enabled during download.
- Return type:
bool
- Returns:
Trueif this instance is enabled during download; otherwise,False.
- update(type: int, id: str, version: str, module: str = None)¶
Updates the specified device.
- Parameters:
type (int) – The device type.
id (str) – The device identification.
version (str) – The device version.
module (str) – The module ID. (This parameter is optional.)
- plug(name: str, type: int, id: str, version: str, module: str = None)¶
Plugs the specified device.
- Parameters:
name (str) – Name of the device.
type (int) – The device type.
id (str) – The device identification.
version (str) – The device version.
module (str) – The module ID. (This parameter is optional.)
- add(name: str, type: int, id: str, version: str, module: str = None)¶
Adds the specified device.
- Parameters:
name (str) – Name of the device.
type (int) – The device type.
id (str) – The device identification.
version (str) – The device version.
module (str) – The module ID. (This parameter is optional.)
- insert(name: str, index: int, type: int, id: str, version: str, module: str = None)¶
Inserts the specified device at the specified index.
- Parameters:
name (str) – Name of the device.
index (int) – Index where to insert the device.
type (int) – The device type.
id (str) – The device identification.
version (str) – The device version.
module (str) – The module ID. (This parameter is optional.)
- unplug()¶
Unplugs the specified device.
- get_simulation_mode()¶
Gets the simulation mode.
- Returns:
Trueif simulation is enabled.
- set_simulation_mode(simulation)¶
Sets the simulation mode.
- Parameters:
simulation (bool) – if set to
True, simulation is enabled.
- get_gateway()¶
Gets the gateway.
See also:
ScriptDeviceObject.get_device_communication_settings- Return type:
Guid
- Returns:
The guid of the gateway.
- get_address()¶
Gets the address of the device.
See also:
ScriptDeviceObject.get_device_communication_settings- Return type:
str
- Returns:
The device address in the bus independent CODESYS format.
- set_gateway_and_address(gateway: ScriptGateway, address: str)¶
Sets the gateway and address.
If you pass the empty gateway and an empty address, the gateway address will be cleared. You can use
ScriptGateway.find_address_by_ip()to search the CODESYS address when you know the ip address or hostname.- Parameters:
gateway (
ScriptGateway) – The gateway.address (str) – The address in the bus independent CODESYS format.
- get_module_identification()¶
Returns the unique identification of a module.
A module is a special type of device, that is only available within the context of a certain device. The module is identified by the same values as each owning device, with an additional module id, to distinguish it from other modules of the same device.
Examples for modules are device local io modules and similar nodes.
- Version added:
3.4.4.0
- Return type:
str
- Returns:
The module identification, or an empty string if this module has no module identification.
- allow_interfaces_at(index)¶
Get the name of the child interfaces that this device object can accept at the specified insert position.
- Version added:
3.5.4.0
- Parameters:
index (int) – The child index where a device should be inserted.
- Return type:
list[str]
- Returns:
A list of possible interface names or
Noneif no device can be inserted at that position.
- property device_parameters¶
Gets the set of device parameters.
Since V3.5.8.0, this actually is a
ScriptMappableDeviceParameterSet.- Version added:
3.5.4.0
- Return type:
ScriptDeviceParameterSet
- property connectors¶
Gets the connectors.
- Return type:
ScriptDeviceConnectorSet
- set_gateway_and_device_name(gateway: str, device_name: str)¶
Sets the gateway and device name for communication.
If you pass the empty guid and an empty address, the gateway address will be cleared. The device will be tracked by its device name - when trying to go online, a quick online scan will be made and the first device with the given name will be selected.
- Version added:
3.5.8.0
- Parameters:
gateway (str) – The gateway Guid(as string) or its name.
device_name (str) – The device name.
- set_gateway_and_ip_address(gateway: str, ip_address: IPAddress, port: int = 11740)¶
Sets the gateway and IP address for communication.
- Version added:
3.5.8.0
- Parameters:
gateway (str) – The gateway guid (as string) or name.
ip_address (IPAddress) – The IP Address.
port (ushort) – The port. Omit to use the default port 11740.
- Raises:
InvalidOperaionException – If
gatewayis passed as a string and several gateways have the same name.
- get_device_communication_settings()¶
Gets the communication settings of the device.
- Return type:
- export_io_mappings_as_csv(file_path)¶
Export the io mappings as a CSV file to the specified absolute path.
- Version added:
3.5.8.0
- Parameters:
file_path (str) – The absolute path of the file to export.
- import_io_mappings_from_csv(file_path)¶
Imports the io mappings from a CSV file at the specified absolute path.
- Version added:
3.5.8.0
- Parameters:
file_path (str) – The absolute path of the file to import.
- property driver_info¶
Get the driver info of the device.
- Version added:
3.5.9.0
- Return type:
- property allow_symbolic_var_access_in_sync_with_iec_cycle¶
Property used by the symbol configuration to determine if symbolic variable access is allowed to be synchronized with the IEC cycle.
The default is False and should be kept for most use cases. Setting this to
Truemay increase the jitter for all applications running on the device because the task accessing the variables may block other tasks. The device object has to supportDeviceObject(3.5.10.0) to access the value.- Version added:
3.5.10.0
- Return type:
bool
- class ScriptDeviceObject.ScriptProjectDeviceExtension¶
Bases:
objectFunctionality to add top-level devices (e. G. SPS) to projects.
ScriptProject instances are amended with these objects.
- Version added:
3.4.3.0
- add(name: str, type: int, id: str, version: str, module: str = None)¶
Adds the specified device.
- Parameters:
name (str) – Name of the device.
type (int) – The device type.
id (str) – The device identification.
version (str) – The device version.
module (str) – The module ID. (This parameter is optional.)
- class ScriptDeviceObject.DeviceId¶
Bases:
objectRepresents a Device ID.
An implementation class of this interface is injected under the name “DeviceID” into the python scope, so python code can create device IDs without the need to subclass that interface. The constructor signature is: DeviceID(int iType, string stId, string stVersion)
- property type¶
Type of the device.
- Return type:
int
- property id¶
Id of the device.
The format for this id is specified for each type. The id is unique within the class of devices of one type.
- Return type:
str
- property version¶
The version of the device.
The format for the version string is specified for each type.
- Return type:
str
- class ScriptDeviceObject.ModuleId¶
Bases:
DeviceIdUnique identification for a module.
A module is a special type of device, that is only available within the context of a certain device. The module is identified by the same values as each owning device, with an additional module id, to distinguish it from other modules of the same device.
Examples for modules are device local io modules and similar nodes.
- property module_id¶
Id of the module.
The format for this id is specified for each type. The id is unique within the class of devices of one type.
- Return type:
str
- class ScriptDeviceObject.ScriptCommunicationSettings¶
Bases:
objectProvides access to the communication settings of the device.
- property gateway_guid¶
The guid of the gateway.
- Return type:
Guid
- property device_address¶
The address of the device.
- Return type:
str
- property prompt_at_login¶
Whether there’s a prompt at login.
- Return type:
bool
- property secure_online_mode¶
Gets a boolean value indicating whether secure online mode is activated for the corresponding devices.
If set, user interfaces should prompt the user before an operation is executed which changes the state of the controller.
- Return type:
bool
- property device_name¶
Gets the name of the device as entered on the communication settings page.
- Return type:
str
- property monitoring_interval_msec¶
The interval for status and variable monitoring measured in milliseconds.
Default = 200ms, Minimum = 10ms, Maximum = 1000ms, Increment 10ms. Invalid values will be ignored
- Return type:
int
- property monitoring_interval¶
The interval for status and variable monitoring measured in milliseconds.
Default = 200ms, Minimum = 10ms, Maximum = 1000ms, Increment 10ms. Invalid values will be ignored
- Return type:
TimeSpan
- property TrackingMode¶
Property to get the mode used to track a device on the network - whether the device is tracked via CODESYS address, ip address or name.
- Return type:
- property scanned_device_name¶
The name of the physical device (E.g. “MyPlc”), as seen in the network scan.
- Return type:
str
- property scanned_ip_address_and_port¶
Device IP Address and Port if block driver TCP is used for connection.
Format: “192.168.101.109:11740”, as seen in the network scan.
This may return the emtpy string if it’s not available. Even if some network scan members are set, this does not guarantee that all of them are set.
- Return type:
str
- property scanned_target_id¶
Target ID.
Format: “1234 ABCD” (=hexadecimal), same as in device description, as seen in the network scan.
This may return the emtpy string if it’s not available. Even if some network scan members are set, this does not guarantee that all of them are set.
- Return type:
str
- property scanned_target_name¶
The name of the target (E.g. “CODESYS PLC Win NT”), as seen in the network scan.
This may return the emtpy string if it’s not available. Even if some network scan members are set, this does not guarantee that all of them are set.
- Return type:
str
- property scanned_target_type¶
Target Type (Format: “4096” (=decimal), same as in device description), as seen in the network scan.
This may return the emtpy string if it’s not available. Even if some network scan members are set, this does not guarantee that all of them are set.
- Return type:
str
- property scanned_target_vendor¶
The vendor of the target, as seen in the network scan.
This may return the emtpy string if it’s not available. Even if some network scan members are set, this does not guarantee that all of them are set.
- Return type:
str
- property scanned_target_version¶
The version of the target, as seen in the network scan.
This may return the emtpy string if it’s not available. Even if some network scan members are set, this does not guarantee that all of them are set.
- Return type:
str
- property is_communication_encrypted¶
Get or set if encrypted communication should be used with the device.
- Version added:
3.5.16.10
- Return type:
bool