Skip to main content

SF_Antivalent

Applicable Safety Standards

SF_Antivalent is a certified PLCopen function block. For detailed information about the applied standards , see: "PLCopen – Technical Committee 5 – Safety Software"

Important

The requirements which are listed in the standards must be met by the user.

Interface Description

This function block converts two antivalent SAFEBOOL inputs (NO/NC pair) to one SAFEBOOL output with discrepancy time monitoring. This FB should not be used stand-alone since it has no restart interlock. It is required to connect the output to other safety related functionalities.

Table 12. VAR_INPUT

Name

Data Type

Initial Value

Description, Parameter Values

Activate

BOOL

FALSE

See General Input Parameters

S_ChannelNC

SAFEBOOL

FALSE

Variable

NC stands for Normally Closed.

Input for NC connection

FALSE: NC contact open

TRUE: NC contact closed

S_ChannelNO

SAFEBOOL

TRUE

Variable

NO stands for Normally Open

Input for NO connection

FALSE: NO contact open

TRUE: NO contact closed

DiscrepancyTime

TIME

T#0ms

Constant

Maximum monitoring time for discrepancy status of both inputs

The cautionary note "DiscrepancyTime" must be observed.



DiscrepancyTime

Applies to developers in Extended Level: The DiscrepancyTime input must be activated with a constant value. As a result, the value must not be changed for the calls.

Table 13. VAR_OUTPUT

Name

Data Type

Initial Value

Description, Parameter Values

Ready

BOOL

FALSE

See General Output Parameters

S_AntivalentOut

SAFEBOOL

FALSE

Safety-related output

FALSE: Minimum of one input signal "not active" or status change outside of monitoring time

TRUE: Both inputs signals "active" and status change within monitoring time.

SafetyDemand

BOOL

FALSE

See General Output Parameters

Error

BOOL

FALSE

See General Output Parameters

DiagCode

WORD

16#0000

See Diagnostic Codes



Tip

"Antivalent" means that during normal operation, the two inputs are in opposite states at the same time. This is sometimes called "complementary" or "non-equivalent".

For certain (lower) levels of safety requirements, it can be allowed to use BOOL as inputs and SAFEBOOL as output. However, this has to be evaluated via the FMEA of the application. In the library, there should be made a distinction between the SAFEBOOL and BOOL version.

Figure 14. Function block: SF_Antivalent
Function block: SF_Antivalent


Functional Description

This function block converts two antivalent SAFEBOOL inputs to one SAFEBOOL output with discrepancy time monitoring. Both inputs are interdependent. The function block output shows the result of the evaluation of both channels.

If S_AntivalentOut = TRUE and one of the safety-related inputs changes, then the output immediately switches to FALSE.

Discrepancy time monitoring: The discrepancy time is the maximum period during which both inputs may have the same states without the function block detecting an error. Discrepancy time monitoring starts when the status of an input changes. The function block detects an error when both inputs have the same values once the discrepancy time has elapsed.

Both inputs must be switched symmetrically. This means that monitoring is performed for both inputs for switching from TRUE to FALSE as well as for switching from FALSE to TRUE.

Table 14. Logic table of inputs/outputs

Inputs

Outputs

Activate

S_ChannelNC

S_ChannelNO

DiscrepancyTime

Ready

S_AntivalentOut

SafetyDemand

Error

DiagCode

FALSE

FALSE

TRUE

Not started

FALSE

FALSE

FALSE

FALSE

16#0000

TRUE

FALSE

TRUE

Not started

TRUE

FALSE

TRUE

FALSE

16#8801

TRUE

FALSE -> TRUE

TRUE

Started

TRUE

FALSE

TRUE

FALSE

16#8802

TRUE

TRUE

TRUE -> FALSE

Started

TRUE

TRUE

FALSE

FALSE

16#8000

TRUE

TRUE

FALSE

Not started

TRUE

TRUE

FALSE

FALSE

16#8000

TRUE

TRUE

FALSE -> TRUE

Started

TRUE

FALSE

TRUE

FALSE

16#8806

TRUE

TRUE -> FALSE

TRUE

Started

TRUE

FALSE

TRUE

FALSE

16#8801

TRUE

FALSE

TRUE

Not started

TRUE

FALSE

TRUE

FALSE

16#8801

TRUE

FALSE

TRUE -> FALSE

Started

TRUE

FALSE

TRUE

FALSE

16#8804

TRUE

FALSE -> TRUE

FALSE

Started

TRUE

TRUE

FALSE

FALSE

16#8000

TRUE

TRUE -> FALSE

FALSE

Started

TRUE

FALSE

TRUE

FALSE

16#8806

TRUE

FALSE

FALSE -> TRUE

Started

TRUE

FALSE

TRUE

FALSE

16#8801



Tip

In the logic table, an arrow -> stands for a transition. TRUE -> FALSE means that the value of the variable has changed from TRUE to FALSE.

State diagram

Figure 15. State diagram: SF_Antivalent
State diagram: SF_Antivalent


Tip

The transition from any state to the Idle state due to Activate = FALSE is not shown. However these transitions have the highest priority.

Typical Timing Diagrams

Figure 16. Timing diagram 1: SF_Antivalent
Timing diagram 1: SF_Antivalent


Figure 17. Timing diagram 2: SF_Antivalent
Timing diagram 2: SF_Antivalent


Error Detection

The function block monitors the discrepancy time between Channel NO and Channel NC.

Error Behavior

The output S_AntivalentOut is set to FALSE. Error is set to TRUE. DiagCode indicates the Error states. There is no Reset defined as an input coupled with the reset of an error. As soon as a Set of input values with the correct S_AntivalentOut is present, Error is FALSE again.

FB-Specific Error and State Codes

Table 15. FB-specific error codes

DiagCode

State Name

State Description and Output Setting

16#C010

Error 1

Discrepancy time elapsed in state 16#8802

Ready = TRUE

S_AntivalentOut = FALSE

SafetyDemand = FALSE

Error = TRUE

16#C020

Error 2

Discrepancy time elapsed in state 16#8804

Ready = TRUE

S_AntivalentOut = FALSE

SafetyDemand = FALSE

Error = TRUE

16#C030

Error 3

Discrepancy time elapsed in state 16#8806

Ready = TRUE

S_AntivalentOut = FALSE

SafetyDemand = FALSE

Error = TRUE



Table 16. FB-specific state codes

DiagCode

State Name

State Description and Output Setting

16#0000

Idle

The function block is not active (initial state).

Ready = FALSE

S_AntivalentOut = FALSE

SafetyDemand = FALSE

Error = FALSE

16#8801

Init

An activation has been detected by the FB and the FB is now activated.

Ready = TRUE

S_AntivalentOut = FALSE

SafetyDemand = TRUE

Error = FALSE

16#8000

Safety Output Enabled

The inputs are switched to TRUE in antivalent mode.

Ready = TRUE

S_AntivalentOut = TRUE

SafetyDemand = FALSE

Error = FALSE

16#8802

Wait for NO

ChannelNC has been switched to TRUE – waiting for ChannelNO to be switched to FALSE; discrepancy timer started.

Ready = TRUE

S_AntivalentOut = FALSE

SafetyDemand = TRUE

Error = FALSE

16#8804

Wait for NC

ChannelNO has been switched to FALSE – waiting for ChannelNC to be switched to TRUE; discrepancy timer started.

Ready = TRUE

S_AntivalentOut = FALSE

SafetyDemand = TRUE

Error = FALSE

16#8006

From Active Wait

One channel has been switched to inactive; waiting for the second channel to be switched to inactive too.

Ready = TRUE

S_AntivalentOut = FALSE

SafetyDemand = TRUE

Error = FALSE