IOL_AdjustableSwitchingSensor (FB)¶
FUNCTION_BLOCK IOL_AdjustableSwitchingSensor
- InOut:
Scope
Name
Type
Comment
Input
xExecute
BOOL
A trigger causes the function selected with variable Function to be executed
ID
DWORD
Addresses the IO-Link proxy Submodule i.e. IO-Link Master or IO-Link Device
Port
BYTE
Port number
BackupEnable
BOOL
“true” = Data Storage enabled; “false” = disabled
Func
This variable selects the functionality to be triggered by a Request(INT) 0 = no_func; 1 = rd_all; 2 = wr_conf; 3= wr_param; 4 = teachLogicIn
BOOL
This variable defines the value for a new Switchpoint to be written to the sensor on a Request with Function ‘wr_conf’
SetpointIn
INT
This variable defines the value for a new Setpoint to be written to the sensor on a Request with Function ‘wr_param’
TeachMode
This variable defines one of the possible teach procedures:(INT) 0 = no_teach; 1 = single_value; 2 = two_value; 3 = dynamicTeachTimer
TIME
Defines the duration of the dynamic teach time
ApplyAuto
BOOL
‘true’ = autoapply_enabled; ‘false’ = autoapply_disabled
TeachRequest
BOOL
A rising edge triggers one step of teach process to be executed according to the selected function at variable TeachFunction.
TeachFunction
The value applied to this variable defines the teach functionality to be executed on TeachRequest. (INT) 0 = no teach; 1 = teach 1; 2 = teach 2; 3 = appply; 4 = abort
Output
xDone
BOOL
The signal is set, if the FB has completed a requested operation.
xBusy
BOOL
The signal is set, if the FB is executing a requested operation.
xError
BOOL
The signal is set, if an error occurred during execution of a requested operation.
PNIOStatus
DWORD
PNIOStatus Information of RDREC and WRREC
IOL_Status
DWORD
Status Information of IOL_Device
Status
(WORD) Current status of the FB operation and executed functions.
LogicOut
BOOL
Represents the current value of the parameter Logic from the sensor.
SetpointOut
INT
represents the current value of the parameter Setpoint from the sensor.
PermitTeach1
BOOL
The signal is set, if a teach request for teach function ‘teach_1’ is allowed
PermitTeach2
BOOL
The signal is set, if a teach request for teach function ‘teach_2’ is allowed
PermitApply
BOOL
The signal is set, if a teach request for teach function ‘apply’ is allowed
PermitAbort
BOOL
The signal is set, if a teach request for teach function ‘abort’ is allowed