UpdateDiagnosisEntry (FB)¶
FUNCTION_BLOCK UpdateDiagnosisEntry
This function block is used by a Profinet-Device application to add and remove Profinet diagnosis-data.
The description of ChannelDiagnosisData gives an example how to define device specific diagnosis messages within the GSDML.
The device application adds or removes diagnosis information according to the status of its real periphery.
The real periphery is specified through the diagnosis source (API, Slot, Subslot, Channel, Direction, Accumulative).
A diagnosis information (ChannelErrorType, optionally ExtChannelErrorType) exist only once per diagnosis source.
If severity or ExtChannelErrorAddValue changes, the diagnosis information is updated regarding these values.
If the diagnosis of a particular submodule changes during operation (submodule is in data-exchange), a diagnosis alarm is issued to the IO controller owning this submodule.
Update Diagnosis
PROGRAM PLC_PRG VAR ID : UDINT; exec : BOOL; // trigger execution of function block by setting exec := TRUE appears : BOOL := TRUE; updateDiag : ProfinetCommon.UpdateDiagnosisEntry; END_VAR ID := CommFB.SUBSLOT_ID(EN := TRUE, ID := PN_Device.DeviceID, SLOT := 2, SUBSLOT := 1); updateDiag.ID := ID; updateDiag.xAppears := appears; updateDiag.ChannelNumber := 1; updateDiag.ChannelProperties.ChannelType := ProfinetCommon.ChannelProperties_Type.BitSize1; updateDiag.ChannelProperties.Direction := ProfinetCommon.DiagnosisDirection.In; updateDiag.Diagnosis.Severity := ProfinetCommon.DiagnosisSeverity.Fault; updateDiag.Diagnosis.ChannelErrorType := ProfinetCommon.ChannelErrorType.Line_break; //0x0006 Line break updateDiag(xExecute := exec); IF(updateDiag.xDone OR updateDiag.xError) THEN exec := FALSE; END_IF
- InOut:
Scope
Name
Type
Initial
Comment
Input
xExecuteBOOLRising edge: Execute update of submodule’s diagnosis
IDUDINTSubmodule-ID
xAppearsBOOLTRUE: Diagnosis appears - add new diagnosis or update Severity and additional valueFALSE: Diagnosis disappears - clear diagnosis specified by source(Submodule, Channel) and error/ext-errorChannelNumberUINT16#8000
The channel number of the diagnosis source (0x8000 means the whole submodule)
ChannelPropertiesadditional channel data, not used for diagnosis that affect the whole submodule.
DiagnosisThe diagnosis-data entry
Output
xDoneBOOLAction successfully completed
xBusyBOOLFunction block active
xErrorBOOLerror occurred, function block aborts action
StatusError related to local update of diagnosis data, e.g. duplicate entry, no ressource…
PNIOStatusUDINTPNIOStatus of Alarm processing (only with established AR)