ReadNbrSlaves (FB)ΒΆ
FUNCTION_BLOCK ReadNbrSlaves EXTENDS ETrigA
Reads the number of connected slaves
Example:
PROGRAM PLC_PRG
VAR
readnbr : ReadNbrSlaves;
xRead : BOOL;
wNbrSlaves : WORD;
END_VAR
IF xRead THEN
readnbr.usiCom := DWORD_TO_USINT(Ethercat_Master.InstanceNumber);
readnbr(xExecute := TRUE, udiTimeOut := 1000);
IF readnbr.xDone THEN
xRead := FALSE;
wNbrSlaves := readnbr.wNumberSlaves;
readnbr(xExecute := FALSE);
END_IF
END_IF
- InOut:
Scope
Name
Type
Initial
Comment
Inherited from
Input
xExecuteBOOLRising edge: Action startsFalling edge: Resets outputsIf a falling edge occurs before the function block has completed its action, the outputs operate in the usual manner and are only reset if either the action is completed or in the event of an error. In this case, the corresponding output values (xDone,xError,iError) are present at the outputs for exactly one cycle.ETrigA
xAbortBOOLTRUE: Action is stopped immediately and all outputs are reset to their initial values.ETrigA
Output
xDoneBOOLTRUE: Action successfully completedETrigA
xBusyBOOLTRUE: Function block activeETrigA
xErrorBOOLTRUE: Error occurred, function block aborts actionFALSE: No errorETrigA
xAbortedBOOLTRUE: Action aborted by userETrigA
Input
usiComUSINT1
index of master 1: first Ethercat master
udiTimeOutUDINTTimeout for operation in ms
Output
wNumberSlavesWORDnumber of slaves currently available