ICleanupActionProvider.CleanupAction (METH)

METHOD CleanupAction

CleanupAction is running until one of the following events occurs: When xComplete is TRUE the state STATE.DONE is reached. When xAbort is TRUE the state STATE.ABORTED is reached. When iErrorID ≠ 0 (Zero) the state STATE.ERROR is reached.

After a Ready Condition as input (iErrorIDProposed = 0 and xAbortProposed = FALSE), only the output states
DONE (xComplete is TRUE) or ERROR (iErrorID ≠ 0) are possible.
After a Error Condition as input (iErrorIDProposed ≠ 0), only the output state
ERROR (iErrorID ≠ 0) is possible.
After a Abort Condition as Input (xAbortProposed = TRUE), only the output states
ABORTED (xAbort is TRUE) or ERROR (iErrorID ≠ 0) are possible.

Example

(* common cleanup -- first steps *)

IF xComplete THEN
    IF xAbortProposed THEN
        (* abort condition -- abort specific cleanup *)
        xAbort := TRUE;
        xComplete := FALSE;
    ELSIF iErrorIDProposed <> 0 THEN
        (* error condition -- error specific cleanup *)
        iErrorID := SEL(xComplete, 0, iErrorIDProposed);
        xComplete := FALSE;
    ELSE
        (* ready condition -- done specific cleanup*)
    END_IF
END_IF

(* common cleanup -- last steps *)
InOut:

Scope

Name

Type

Input

xAbortProposed

BOOL

iErrorIDProposed

INT

Output

xComplete

BOOL

xAbort

BOOL

iErrorID

INT