TraceMgrPacketReadNext (FUN)ΒΆ

FUNCTION TraceMgrPacketReadNext : RTS_IEC_HANDLE

Reads the contents of the next record.

Note

if the result code is ERR_ENTRIES_REMAINING, data has been successfully copied to pTraceBuffer, but more data can be read by a subsequent call. (Either because the destination buffer was too small, or because new data has been recorded in the mean time.)

Note

Data is always returned in little endian byte order even if the device has big endian byte order.

InOut:

Scope

Name

Type

Comment

Return

TraceMgrPacketReadNext

RTS_IEC_HANDLE

Returns the runtime system error code (see CmpErrors.library):
  • ERR_PARAMETER if hPacket is not a valid packet handle or if hPrevRecord is not a valid record handle

  • ERR_NO_OBJECT if there is no next record

  • ERR_NOTINITIALIZED if the packet is not complete

  • ERR_TIMEOUT if reading took too long

  • ERR_ENTRIES_REMAINING if more data can be read by a subsequent call (this is not an error)

Input

hPacket

RTS_IEC_HANDLE

The trace packet handle

hPrevRecord

RTS_IEC_HANDLE

The trace record handle of the current record

Inout

pTraceBuffer

TraceRecordEntry

Pointer to the destination buffer

pulReadBytes

UDINT

Size of the destination buffer in bytes (in), number of bytes copied (out)

pResult

RTS_IEC_RESULT

The result code